SPX advanced – description of parameters
SPX ADVANCED APPLICATION MANUAL
SVCH0203—October 2017 www.eaton.com
Code
ID
Description
Notes
P1.13.21
1440
Control slot selector “ControlSlotSel.”
5 = Slot E
6 = Slot D, Fast fieldbus support
7 = Slot E, Fast fieldbus support
Restrictions when Fast fieldbus support is activated:
1. Set first the Slave Address and the PPO type before selecting the Fast fieldbus mode
2. Fast fieldbus profile is not available for all fieldbus board, contact factory for more
detail
3. Service data of profibus board cannot be used
4. Fieldbus board parameters cannot be accessed
5. Profibus option board will operate only in ByPass mode
6. Standard F53 fault detection is not available. WD Pulse monitoring needs to be used
to monitor communication faults
P1.13.22
State machine
Application has possibility to select what kind of state machine is used.
1: Standard
This mode makes fieldbus control behave as in explained in used fieldbus board
manual.
2: ProfiDrive
This mode uses ProfiDrive type state machine in application level. This mode is
possible to use on fieldbus boards that does not have state machine itself or has
possibility to bypass state machine functionality in option board.
See chapter 9: Status and Control Word in detail
P1.13.23
898
Fieldbus custom minimum “FB custom min”
P1.13.24
899
Fieldbus custom maximum “FB custom max”
With these parameters its possible to define fieldbus reference input values scaling.
default is 0...10000 (0...100%)
Code
ID
Description
Notes
P1.14.1.1
1580
Control input signal ID “ContrInSignal ID”
With this parameter you can select what signal is used tocontrol selected parameter.
P1.14.1.2
1581
Control off limit “Contrl off limit”
This parameter defines the limit when the selectedparameter value is forced to Off
value.
P1.14.1.3
1582
Control on limit “contrl on limit”
This parameter defines the limit when the selected parameter value is forced to On
value.
P1.14.1.4
1583
Control off value “contrl off value”
This parameter defines the value that is used when the used input signal is below
Off limit.
P1.14.1.5
1584
Control on value“Contrl on value”
This parameter defines the value that is used when the used input signal is above On
limit.
P1.14.1.6
1585
Control output signal“ContrlOutSignID”
This parameter defines which parameter is forced to On and Off values when selected
input signal exceeds the set limits.
P1.14.1.7
1586
Control mode ID1586 “control mode”
This parameter defines how the value control output behaves. 0 = SR ABS
Absolute input value is used to make a step change in the output between On and Off
values.
5.15 ID functions
Listed here are the functions that use the parameter ID
number to control and monitor the signal.
5.15.1 Value control
The value control parameters are used to control an input
signal parameter.