13
SPX Advanced application – monitoring values
SPX ADVANCED APPLICATION MANUAL
SVCH0203—October 2017 www.eaton.com
System bus status word ID1601
False
True
b10
Drive 3 running
b11
Drive 3 fault
b12
Drive 4 in synch
b13
Drive 4 ready
b14
Drive 4 running
b15
Drive 4 fault
V7.26.2
Total current
A
ID 80
D1: This value is the current of whole drive
synch system.
D2, D3 and D4:This value is the sum current
of the drive’s own power unit and that of the
drives with smaller system bus identification
number starting from master drive.
If D2 Master: This value is the current of whole
drive synch system.
V7.26. 3
Master CW
ID93
Master Drive Control Word. Master Sending,
Follower receiving.
Master control word ID93
Master-follower
DriveSynch master-follower
b0
Ready status
b1
Run enable
b2
Final run request
b3
Fault reset
Fault reset
b4
Running
Running
b5
Fault
b6
Brake control
Brake control
b7
WD Pulse
b8
Brake control reference release
b9
Data logger trigger
Data logger trigger
b10
Ramp stop active
b11
Start delay active
b12
b13
b14
Disable SB diagnostic
Disable SB diagnostic
b15
V7.26.4.1
Motor current D1
A
ID 1616
D1, D2, D3 and D4: This value is the current of
drive own power unit.
V7.26.4.2
Motor current D2
A
ID 1605
D1: This value is the current of drive number
two power unit.
D2, D3 and D4: Not updated.
V7.26.4.3
Motor current D3
A
ID 1606
D1: This value is the current of drive number
three power unit.
D2, D3 and D4: Not updated.
V7.26.4.4
Motor current D4
A
ID 1607
D1: This value is the current of drive number
four power unit.
D2, D3 and D4: Not updated.
V7.26.5.1
Status word D1
ID 1615
D1: Status Word for D1 without B15
D2,D3 and D4: Status Word that is send to D1.
V7.26.5.2
Status word D2
ID 1602
D1: D2 Status Word
D2, D3 and D4: Not updated.
V7.26.5.3
Status word D3
ID 1603
D1: D3 Status Word
D2, D3 and D4: Not updated.
V7.26.5.4
Status word D4
ID 1604
D1: D4 Status Word
D2, D3 and D4: Not updated.
Follower drive status word
False
True
b0
Flux not ready
Flux ready (>90 %)
b1
Not in ready state
Ready
b2
Not running
Running
b3
No fault
Fault
b4
Charge switch open
Charge switch closed
b5
Brake frequency limit on
Brake frequency limit OFF
b6
Run disabled
Run enable
b7
No warning
Warning
b8
Follower
b9
Master
b10
Drive synch In synch
b11
No DC brake
DC Brake is active
b12
No run request
Run request
b13
No limit controls active
Limit control active
b14
External brake control OFF
External brake control ON
b15
Heard beat
3.2.4 PI Control monitoring
This PI control uses ID numbers for input and output signal.
See detail in PI Control chapter.
V7.27.1
PI Reference
ID20
Used PI Reference, reference is selected by
ID number.