SPX advanced – description of parameters
SPX ADVANCED APPLICATION MANUAL
SVCH0203—October 2017 www.eaton.com
B08: FALSE = Speed Error Out Of Tolerance Range, TRUE =
Speed Error Within Tolerance Range
Speed Error Out Of Tolerance Range:
Speed Error Within Tolerance Range:
B09: FALSE = No Control Requested, TRUE =
Control Requested
No Control Requested: Control by the automation system is
not possible, only possible
at the device or by another interface.
Control Requested: The automation system is requested to
assume control.
B10: FALSE = f Or n Not Reached, TRUE = f Or n Reached
Or Exceeded
f Or n Not Reached: Speed is below P1.6.4.5 Above
Speed Limit.
f Or n Reached Or Exceeded: Speed is above P1.6.4.5
Above Speed Limit.
B15: FALSE = FB DW Feedback Low, TRUE = FB DW
Feedback High
FB DW Feedback: FB Control Word B11 is echoed back to
the Fieldbus. Can be use to monitor communication status
from the drive.
8.3 Combination 3, ByPass – basic
8.3.1 Control word combination 3, ByPass – basic
Main Control Word for Profibus in Combination 3
False
True
Comment
b0
STOP
START
b1
Clockwise
Counter clockwise
b2
No action
FAULT RESET (0 -> 1)
b3
FB DIN1
FB DIN1
b4
FB DIN2
FB DIN2
b5
FB DIN3
FB DIN3
b6
FB DIN4
FB DIN4
b7
FB DIN5
FB DIN5
b8
Not used
Not used
b9
Not used
Not used
b10
Not used
Not used
b11
Not used
Not used
b12
Not used
Not used
b13
Not used
Not used
b14
Not used
Not used
b15
Not used
Not used