84
SPX advanced – description of parameters
SPX ADVANCED APPLICATION MANUAL
SVCH0203—October 2017 www.eaton.com
Code
ID
Parameter
Notes
P1.5.3.2
1520
Analog output 4, function “Iout 4 content”
12 “(-2Tn)-(2Tn)”
Motor torque from negative two times motor nominal to positive two times motor
nominal torque
13 “(-2Pn)-(2Pn)”
Motor power from negative two times motor nominal to positive two times motor
nominal power
14 “PT100 Temp.”
Maximum PT100 temperature value from used input scaling from -30 C to +200 C
15 “FB Data In4”
FB analog output fieldbus process data value can be connected to analog output
by using monitoring signal ID48.
16 “(-2nN)-(2nN)”
Motor speed from negative two times nominal to positive two times nominal
speed
17 “Enc 1 speed”
Encoder 1 speed from zero speed to motor synchronous speed
18 “Unit temp”
Unit temperature scaled from 0 degree to 100 degree.
19 “Value control”
Value control output
20 “Drive output power”
Drive output power scaled from zero to Motor nominal power (P1.1.8).
P1.5.2.3
308
Analog output filter time “Iout Filter time”
P1.5.3.3
473
Analog output 2 filter time “Iout 2 Filter T”
P1.5.4.3
480
Analog output 3, filter time “Iout 3 Filter T”
P1.5.5.3
1521
Analog output 4, filter time “Iout 4 Filter T”
First order filtering is used for analog output signals.
0
2000
4000
6000
8000
10000
12000
-0
.04
5
0.
54
5
1.
13
5
1.
72
5
2.
31
5
2.
90
5
3.
49
5
4.
08
5
4.
67
5
5.
26
5
5.
85
5
6.
44
5
Unfiltered
1 s filter time
63 %
P1.5.2.4
309
Analog output inversion “Iout Invert”
P1.5.3.4
474
Analog output 2 inversion “Iout 2 invert”
P1.5.4.4
481
Analog output 3 inversion “Iout 3 invert”