60
SPX advanced – description of parameters
SPX ADVANCED APPLICATION MANUAL
SVCH0203—October 2017 www.eaton.com
Code
ID
Parameter
Notes
P1.2.11.3
366
Motor potentiometer reference copy “MotPotRefCopy”
This parameter defines how reference is handled when reference input is changed to
motor potentiometer in I/O control.
0 “No copy”
Reference is not copied. Depending on “MotPot Reset” function, the drive may start
from minimum frequency or from reference that was last used when the drive was run
with motor potentiometer.
1 “Reference”
The drive’s active reference is copied. If the drive is ramping when the value of
motor potentiometer is changed the drive will continue ramping after the change.
This allows the reference copy in stop state unless the “MotPot Reset” function
overruns it (e.g. reset in stop state is not selected).
2 “Freq. Output”
Speed at the time of change is copied to reference. If the drive is ramping when the
change is made the drive will stop ramping and keep the present speed.
5.2.7 Adjust reference
Adjust reference function is used to fine tune the main
reference. Adjust reference is added to main reference after
“SpeedShare” function “See Figure below”
Adjust Input
Not Used
Analogue Input 1
Analogue Input 2
Analogue Input 3
Analogue Input 4
FB Adjust Reference
P
MUX
C
P
ADD
+
+
+
FW
MULDIV
SUB
MULDIV
10000
C
10000
F
Adjust Reference
FreqRef1
VALUE
IN 1
VALUE
MULTIP
DIVIS
IN 2
MULTIP
DIVIS
Adjust Min
P
Adjust Min
P
Adjust Max
K
IN 0
IN 1
IN 2
IN 3
IN 4
IN 5
F
F
F
F
F
F
Code
ID
Parameter
Notes
P1.2.12.1
493
Adjust input “adjust input”
With this parameter you can select the signal according to which the frequency
reference to the motor is fine adjusted.
0 Not used
1 Analog input 1
2 Analog input 2
3 Analog input 3
4 Analog input 4
5 FB Adjust Reference ID47 Monitoring Signal
P1.2.12.2
494
Adjust minimum “adjust minimum”
Percentage that is subtracted from the main reference when adjust input is at
minimum.