29
SPX Advanced application – parameter list
SPX ADVANCED APPLICATION MANUAL
SVCH0203—October 2017 www.eaton.com
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.6.5.3
Brake chopper
0
4
0
504
0=Disabled
1=Used when running
2=External brake chopper
3=Used when stopped/running
4=Used when running (no testing)
P1.6.5.4
Brake chopper level
5: 605
6: 836
5: 797
6: 1099
V
1267
P1.6.5.5
Under voltage controller
0
2
1
608
0=Not used
1=Used (no ramping)
2=Used (ramping to zero)
P1.6.5.6
Under voltage ref selector
0
1
1
1537
0=Under Voltage Ref
1= 0.8 * Estimated DC volt.
P1.6.5.6
Under voltage reference
5: 410
6: 567
5: 540
6: 745
V
Varies
1538
4.6.5.1 DC-link handling CL settings
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.6.5.8.1 Over voltage reference
94.00
130.00
%
118.00
1528
P1.6.5.8.2 Over voltage motoring side
torque limit
0.0
300.0
%
10.0
1623
Maximum motoring torque when over voltage controller is active.
P1.6.5.8.3 CL Under voltage reference
60.00
80.00
%
65.00
1567
4.6.6 Limit settings options
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.6.6.1
Limit total current
in closed loop
0
1
0
1901
0=No
1=Yes
4.6.7 Limit settings options
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.6.7.1
Current regulator response
0
1
1
757
0=No action
1=Warning
P1.6.7.2
Overvoltage regulator
response
0
1
1
758
0=No action
1=Warning
P1.6.7.3
Under voltage regulator
response
0
1
1
759
0=No action
1=Warning
P1.6.7.4
Torque regulator response
0
1
1
760
0=No action
1=Warning
4.7 Flux and DC current handling
4.7.1 Flux and DC current handling OL settings
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.7.1.1
DC braking current
0.00
I
L
A
0.00
507
P1.7.1.2
DC braking time at start
0.00
600.00
s
0.00
516
0=DC brake is off at start
P1.7.1.3
DC braking time at stop
0.00
600.00
s
0.00
508
0=DC brake is off at stop
P1.7.1.4
Frequency to start DC braking
during ramp stop
0.10
10.00
Hz
1.50
515
P1.7.1.5
Scaling of DC-braking current 0
5
0
400
ID46Scaling from 0 to ID507
0=Not used
1=AI1
2=AI2
3=AI3
4=AI4
5=FB Limit scaling