SPX Advanced application – parameter list
SPX ADVANCED APPLICATION MANUAL
SVCH0203—October 2017 www.eaton.com
4.15.1.1 Brake control start up torque for CL
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.15.12.1 Start-up torque
0
3
0
621
0=Not used
1=Torque memory
2=Torque reference
3=Start-up torque fwd/rev
P1.15.12.2 Start-up torque FWD
–300.0
300.0
s
0.0
633
P1.15.12.3 Start-up torque REV
–300.0
300.0
s
0.0
634
P1.15.12.4 Start Up Torque Time
–1
10000
ms
–1
1371
–1 = Automatic
4.15.1.2 Roll back control for CL
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.15.13.1 Roll back Kp
1787
P1.15.13.2 Roll back torque
1788
P1.15.13.3 Roll back level
1789
4.16 Auto restart parameters
Table 45 . Auto restart parameters, G1 .16
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.16.1
Wait time
0.10
10.00
s
0.50
717
P1.16.2
Trial time
0.00
60.00
s
0.10
718
P1.16.3
Start function
0
2
2
719
0=Ramp
1=Flying start
2=According to stop function
P1.16.4
Number of tries after
undervoltage trip
0
10
0
720
P1.16.5
Number of tries after
overvoltage trip
0
10
0
721
P1.16.6
Number of tries after
overcurrent trip
0
3
0
722
P1.16.7
Number of tries after
reference trip
0
10
0
723
P1.16.8
Number of tries after motor
temperature fault trip
0
10
0
726
P1.16.9
Number of tries after external
fault trip
0
10
0
725
P1.16.10
Number of tries after
underload fault trip
0
10
0
738
P1.16.11
Number of tries after
cooling fault
0
10
0
731
P1.16.12
Number of tries after O/P
contactor fault
0
10
0
735
P1.16.13
Fault simulation
0
65535
0
1569
4.17 PID
4.17.1 PID basic settings
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.17.1.1 PID Controller gain
0
1000.0
%
100.0
118
P1.17.1.2 PID Controller I Time
0
320.00
s
1.00
119
P1.17.1.3 PID Controller D Time
0
100.00
s
0.00
132