21
SPX Advanced application – parameter list
SPX ADVANCED APPLICATION MANUAL
SVCH0203—October 2017 www.eaton.com
Code
Parameter
Min
Default
ID
Note
P1.4.2.27 Inching 2
0.1
0.1
531
Inching reference 2 (default reverse –2 Hz.
See P1.4.17). This will start the drive.
P1.4.2.28 Motoring power limit 1
0.1
0.1
1500
Activates power limit 1
P1.4.2.29 Motoring power limit 2
0.1
0.1
1501
Activates power limit 2
P1.4.2.30 2
nd
frequency limit
0.1
0.1
1511
Activates second freq. Limit
P1.2.7.31 2
nd
Freq Limit
P1.4.2.31 Generator power limit 1
0.1
0.1
1506
Activates Gen. power limit 1
P1.4.2.32 Generator power limit 2
0.1
0.1
1507
Activates Gen. power limit 2
P1.4.2.33 Reset position
0.1
0.1
1090
P1.4.2.34 MF mode 2
0.1
0.1
1092
P1.4.2.35 Emergency stop
0.1
0.2
1213
P1.4.2.36 Motoring torque limit 1
0.1
0.1
1624
P1.4.2.37 Generator torque limit 1
0.1
0.1
1626
P1.4.2.38 Store parameter set
0.1
0.1
1753
Stores active parameter set to selected parameter set
P1.4.2.39 Start signal 1B
0.1
A.1
403
Forward, See ID300
P1.4.2.40 Start signal 2B
0.1
A.2
404
Reverse. See ID300
P1.4.2.41 RunRequest enable
0.1
0.2
1896
P1.4.2.42 Output contactor interlock
0.1
0.2
1600
Faults if contactor does not close within 250ms after run
P1.4.2.43 PID Set point 1/2
0.1
0.1
1601
4.4.3 Analog input 1
Table 7 . Analog input 1 parameters, G1 .2 .3
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.4.3.1
AI1 signal selection
0.1
E.10
A.1
377
Slot . Board input No.
P1.4.3.2
AI1 Reference filter TC
0.000
32.000
s
0.000
324
0=No filtering
P1.4.3.3
AI1 signal range
0
3
0
320
0=0…100%*
1=20…100%* 4 mA Fault
2= –10V…+10V*
3= Custom range*
P1.4.3.4
AI1 custom minimum setting –160.00
160.00
%
0.00
321
Custom range: Minimum input
P1.4.3.5
AI1 custom maximum setting –160.00
160.00
%
100.00
322
Custom range: Maximum input
P1.4.3.6
AI1 reference scaling.
minimum value
0.00
320.00
Hz
0.00
303
Selects the frequency that corresponds to the min. reference signal
P1.4.3.7
AI1 reference scaling.
maximum value
0.00
320.00
Hz
0.00
304
Selects the frequency that corresponds to the max. reference signal
P1.4.3.8
AI1 joystick dead zone
0.00
20.00
%
0.00
382
Dead zone for joystick input
P1.4.3.9
AI1 sleep limit
0.00
100.00
%
0.00
385
Drive goes to stop if input is below this limit for this time.
P1.4.3.10 AI1 sleep delay
0.00
320.00
s
0.00
386
Drive goes to stop if input is below this limit for this time.
P1.4.3.11 AI1 joystick offset
–100.00
100.00
%
0.00
165
Press enter for 1s to set offset
P1.4.3.12 AI1 filter time
0.000
32.000
s
0.000
1228
4.4.4 Analog input 2
Table 8 . Analog input 2 parameters, G1 .2 .4
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.4.4.1
AI2 signal selection
0.1
E.10
A.2
388
Slot . Board input No.
P1.4.4.2
AI2 filter time
0.000
32.000
s
0.000
329
0=No filtering
P1.4.4.3
AI2 signal range
0
3
1
325
0=0…100%*
1=20…100%* 4 mA Fault
2= –10V…+10V*
3= Custom range*
P1.4.4.4
AI2 custom minimum setting –160.00
160.00
%
0.00
326
Custom range: Minimum input