SPX Advanced application – monitoring values
SPX ADVANCED APPLICATION MANUAL
SVCH0203—October 2017 www.eaton.com
3.2 Monitoring values description
otee:
N
for DriveSynch Systems:
In a DriveSynch system, only Master drive monitoring
signals are reliable.
Only directly measured values are reliable in follower units.
Even the Output Frequency of DriveSynch follower is not
directly observed and thus may not show actual output
frequency that is controlled by DriveSynch Master Drive.
V7.1
Output frequency
[#,## Hz] ......ID1
Output frequency to motor, updated at 10 ms
time level.
V7.2
Frequency reference
[#,## Hz] ......ID 25
Frequency reference to motor control, after
speed share function. updates at 1 ms time level.
V7.3
Motor speed
[ # rpm]
ID 2
Motor speed in rpm
V7.4
Motor current
[A] ...............ID 3
Open loop:
1 s linear filtering.
Closed loop:
32 ms filtering
Drive Synch Operation Master drive:
This value is the total current of the system
divided by number of drives in the system
(SbLastID). SbLastId cannot be changed;
it needs to be set according to how many
drives are linked with system bus.
Drive Synch Operation Follower drive:
This value is the current of the drive’s own
power unit.
Current scaling in different size of units
otee:
N
ID45, usually in Process data OUT 3 is scaled to be
with one decimal always.
Voltage
Size CT amps
Scale
208 – 240 Vac
0001 – 0011
100 – 0.01A
208 – 240 Vac
0012 – 0420
10 – 0.1A
208 – 240 Vac
0530
1 – 1A
380 – 500 Vac
0003 – 0007
100 – 0.01A
380 – 500 Vac
0009 – 0300
10 – 0.1A
380 – 500 Vac
0385 – 2643
1 – 1A
525 – 690 Vac
0004 – 0013
100 – 0.01A
525 – 690 Vac
0018 – 0261
10 – 0.1A
525 – 690 Vac
0325 – 1500
1 – 1A
V7.5
Motor torque
%
ID 4
In % of Motor nominal torque
Open loop:
1 s linear filtering
Closed loop:
32 ms filtering
Drive Synch Operation Follower drive:
This value is the torque of the drive’s own
power calculated in open loop. Motor torque is
valid only in Master drive.
V7.6
Motor power
%
ID 5
Calculated motor power
V7.7
Motor voltage V
ID 6
Calculated motor voltage
V7.8
DC link voltage V
ID 7
Measured DC voltage, filtered.
V7.9
Unit temperature oC
ID 8
Heatsink temperature
V7.10
Motor temperature
%
ID 9
Calculated motor temperature
105 % is tripping limit if response is fault.
V7.11
Analog input 1
%
ID 13
V7.12
Analog input 2
%
ID 14
Unfiltered analog input level.
0 % = 0 mA/0 V, –100 % = –10 V, 100 %
= 20 mA/10 V.
Monitoring scaling is determined by the option
board parameter.
V7.13
Analog input 3
%
ID 27
V7.14
Analog input 4
%
ID 28
It is possible to adjust this input value from
fieldbus when the input terminal selection is 0.1.
This way it is possible to adjust the free analog
input from fieldbus and have all analog input
functions available for fieldbus process data.
V7.15
Analog out 1
%
ID 26
V7.16
Analog out 2
%
ID 31
V7.17
Analog out 3
%
ID 32
V7.18
Analog out 4
%
ID 1526
Analog Output value 0 % = 0 mA/0 V, 100 %
= 20 mA/10 V
V7.19
DIN1, DIN2, DIN3
ID 15
V7.20
DIN4, DIN5, DIN6
ID 16
DIN1/DIN2/DIN3 status
DIN4/DIN5/DIN6 status
b0
DIN3
DIN6
b1
DIN2
DIN5
b2
DIN1
DIN4
V7.21
Power reference
%
ID 1700
Power reference monitoring value. If power
reference is not selected in the reference
group it can be directly written to this
monitoring variable from fieldbus and only
ramping rate function is active from power
reference group.
V7.22
PT-100 Temperature Cº
ID 42
Highest temperature of OPTB8 board. 4 s filtering.