SPX advanced – description of parameters
SPX ADVANCED APPLICATION MANUAL
SVCH0203—October 2017 www.eaton.com
Code
ID
Description
Notes
P1.12.2.5
742
Board 1 fault limit “Board1 fault Lim.”
Set here the limit at which the PT100 fault (F56) will be activated.
When individual warning and fault limits are activated this is first board
first channel (1A).
P1.12.2.5
743
Number of used inputs in board 2 “Board2 channels”
If you have two temperature sensor boards installed in your frequency converter you
can choose here the combination inputs in use in the second board. See also the I/O
boards manual.
0 = Not used (ID Write, value of maximum temperature can be written from fieldbus)
1 = Sensor 1 in use
2 = Sensor 1 & 2 in use
3 = Sensor 1 & 2 & 3 in use
4 = Sensor 2 & 3 in use
5 = Sensor 3 in use
P1.12.2.6
766
Board 2 temperature response “Board2 response”
0 = No response
1 = Warning
2 = Fault, stop mode after fault according to Stop Function
3 = Fault, stop mode after fault always by coasting
P1.12.2.7
745
Board 2 warning limit “Board2 Warn. Lim”
Set here the limit at which the second temperature sensor board warning will be
activated. When individual warning and fault limits are activated this is second board
first channel (2A).
P1.12.2.8
746
Board2 fault limit “Board2 FaultLim”
Set here the limit at which the second temperature sensor board fault (F61) will be
activated. When individual warning and fault limits are activated this is second board
first channel (2A).
5.13.2.1 ndividual channel monitoring
Individual channel monitoring is activated by setting one of
the warning limits (per board) different than zero. Common
limits in above parameters will be channel A warning and
fault limits. Channel B and C limits are set with below
parameters.
Code
ID
Description
Notes
P1.12.2.9.1
764
Channel 1B warn
P1.12.2.9.2
765
Channel 1B fault
First board second (1B) channel warning and fault limits.
P1.12.2.9.3
768
Channel 1C warn
P1.12.2.9.4
769
Channel 1C fault
First board third (1C) channel warning and fault limits
.
P1.12.2.9.5
770
Channel 2B warn
P1.12.2.9.6
771
Channel 2B fault
Second board second (2B) channel warning and fault limits.
P1.12.2.9.7
772
Channel 2C warn
P1.12.2.9.8
773
Channel 2C fault
Second board third (2C) channel warning and fault limits
.