10
SPX Advanced application – monitoring values
SPX ADVANCED APPLICATION MANUAL
SVCH0203—October 2017 www.eaton.com
Application status word 2 ID89
False
True
b0
Value control SR = FALSE
Value control SR = TRUE
b1
b2
b3
b4
b5
b6
b7
b8
b9
b10
b11
b12
b13
b14
b15
V7.24.24
Rotor flux
ID1158 “rotor flux”
Calculated rotor flux.
3.2.2 FieldBus monitoring values
V7.25.1
FB Control word ID1160
Control word used in bypass mode.
See P1.13.22 and option board ByPass.
More details in Chapter 9 status and control
word in detail.
Bit
Description
Value = 0
Value = 1
b0
OFF
ON, reset after fault or b1 and b2
b1
Emergency stop by coast
ON, On normal operation: Keep TRUE
b2
Emergency stop by ramp
ON, On normal operation: Keep TRUE
b3
STOP REQUEST
RUN REQUST
b4
Force ramp to zero
Enable ramp,
b5
Freeze ramp
Enable ramp,
b6
Force ref to zero
Enable ramp,
b7
No action
FAULT RESET (0 -> 1)
b8
No action
Inching 1
b9
No action
Inching 2
b10
Disable profibus control
Enable profibus control
b11
Fieldbus DIN1=OFF
Fieldbus DIN1=ON (watchdog pulse)
b12
Fieldbus DIN2=OFF
Fieldbus DIN2=ON
b13
Fieldbus DIN3=OFF
Fieldbus DIN3=ON
b14
Fieldbus DIN4=OFF
Fieldbus DIN4=ON
b15
No action
No action
V7.25.2
FB Status word
ID65
ProfiDrive type status word. Not the same as
used by profibus board in ProfiDrive mode.
Needs to be selected with P1.14.19 GSW to
be used. See detaisl in Chapter 9 status and
control word in detail.
Bit
Description
Value = 0
Value = 1
b0
Not ready to switch on
Ready to switch on
b1
Not ready to operate
Ready to operate
b2
Not running
Running
b3
No Fault
Fault
b4
Coast stop active
Coast stop not active
b5
Quick stop active
Quick stop not active
b6
Switch not inhibited
Switch on inhibit
b7
No warning
Warning
b8
Speed error
Speed at reference
b9
No FB Control request
FB control active
b10
Fout < Fmax
Fout > Fmax
b11
not used
not used
b12
not used
not used
b13
not used
not used
b14
not used
not used
b15
Fieldbus DIN1=OFF
Fieldbus DIN1=ON (Watchdog pulse)
V7.25.3
FB Torque reference
%
ID 1140
Torque reference value from fieldbus.
Default control of FB PD 1
V7.25.4
FB Limit scaling
%
ID 46
Limit scaling input value from fieldbus.
Default control of FB PD 2.
V7.25.5
FB Adjust reference
%
ID 47
Reference adjustment value from fieldbus.
Default control of FB PD 3.
V7.25.6
FB Analog output
%
ID 48
Fieldbus value to control analog output.
Default control of FB PD 4.
V7.25.7
FB Motor current A
ID 45
Motor current (drive independent) given with
one decimal point.
V7.25.8
Fault word 1
ID 1172
Different faults are collected to two words
that can be read from fieldbus or with NCDrive
PC software.
Fault word 1 ID1172
Fault
Comment
b0
Over current or IGBT
F1, F31, F41
b1
Over voltage
F2
b2
Under voltage
F9
b3
Motor stalled
F15
b4
Earth fault
F3
b5
Motor under load
F17
b6
Drive over temperature
F14
b7
Motor over temperature
F16, F56, F29
b8
Input phase
F10
b9
Brake resistor over temperature
F42 (Not implemented)
b10
Device changed
F37, F38, F39, F40, F44, F45
(Not implemented)
b11
Keypad or PCControl
F52
b12
FielBus
F53
b13
SystemBus
F59