SPX advanced – description of parameters
SPX ADVANCED APPLICATION MANUAL
SVCH0203—October 2017 www.eaton.com
Code
ID
Parameter
Notes
P1.5.8.13
357
Analog Low supervision control limit “Ain supv llim”
P1.5.8.14
358
Analog High supervision control limit “Ain supv hlim”
Analogue
Input
DO
High
Limit
Low
Limit
Figure 5-12 . An ex ample of On/Off-control
5.6 Limit settings
5.6.1 Current limit handling
Code
ID
Parameter
Notes
P1.6.1.1
107
Current limit “Current Limit”
This parameter determines the maximum motor current from the AC drive.
The parameter’s value range differs from size to size.
When the Current limit is changed the Stall current limit is internally calculated to 90%
of the current limit (if the Stall current limit is greater than the Current limit). When the
current limit is active the drive output frequency is reduced until current is below the
set limit.
In closed loop control, the current limit affects the torque producing current limit,
not total current. This can be changed in options group with the “LimitTotalCurrent”
parameter.
In drive synch operation limiting is for average current of units.
P1.6.1.2
399
Scaling of current limit “Currnt Lim Sclng”
0 = Not used
1 = AI1
2 = AI2
3 = AI3
4 = AI4
5 = FB Limit Scaling ID46 Monitoring value
This signal will adjust the maximum motor current between 0 and the parameter Motor
Current Limit.
P1.6.1.3
1451
Current limit Kp
P1.6.1.4
1452
Current limit Ki