148
SPX advanced – description of parameters
SPX ADVANCED APPLICATION MANUAL
SVCH0203—October 2017 www.eaton.com
Code
ID
Description
Notes
P1.14.5.1
1216
ID.Bit free digital output control 1 “ID.Bit free DO1”
P1.14.6.1
1386
ID.Bit free digital output control 2 “ID.Bit free DO2”
Select the signal for controlling the DO. The parameter has to be set in format xxxx.
yy where xxxx is the ID number of a signal and yy is the bit number. For example,
the value for DO control is 1174.02. 1174 is the ID number of Warning Word 1. So the
digital output is ON when bit number 02 of the warning word (ID no. 1174) i.e. Motor
underload is high.
P1.14.5.2
1574
Free digital output selector “Free DO1 Sel.”
P1.14.6.2
1325
Free digital output selector “free DO2 sel.”
Select the output terminal to be controlled with the parameter ID.bit Free Digital
output control.
Code
ID
Description
Notes
P1.14.7.1
1832
ID.Bit Free Digital input delay “ID.Bit Free DIN”
Select digital input from DIN Status Word to be delayed.
P1.14.7.2
1833
On Delay “On Delay”
This defines ON delay for the input signal.
P1.14.7.3
1834
Off Delay “Off Delay”
This defines OFF delay for the input signal.
P1.14.7.4
1836
Mono Time“Mono Time”
This timer makes a pulse that last defined time. Pulse will start after On Delay time.
P1.14.7.5
1835
Control Out ID“Control Out ID”
Select the signal ID to be controlled by input signal. If inversion or parameter value
other than zero and one is needed this can be connected to DIN ID Control function
ID1570, ID1590 or 1578 where desired values can be set and connected to correct
parameter.
5.15.4 Free din delay
This function is mend to be used on situation when
certainDIN signal needs On or Off delay before actual
command isgiven. e.g. Reading from DIN Status Word:
DIN1 status givingit a e.g. 1,00 s delay and then writing it
by ID number toID403 Start 1, thus giving 1 second delay to
start in drive side.