97
SPX advanced – description of parameters
SPX ADVANCED APPLICATION MANUAL
SVCH0203—October 2017 www.eaton.com
Code
ID
Parameter
Notes
P1.6.3.9
485
Motoring torque limit scaling “MotTorqLimSclng”
The motoring torque limit is equal to parameter Motoring Torque Limit if value ‘Not
Used’ is selected. If any of the inputs is selected the motoring torque limit is scaled
between zero and parameter Motorin Torque Limit.
0 = Not used
1 = AI1
2 = AI2
3 = AI3
4 = AI4
5 = FB Limit Scaling ID46 Monitoring value
P1.6.3.10
1087
Generating torque limit scaling “GenTorqLimSclng”
The generator torque limit is equal to parameter Generator Torque Limit if value ‘Not
Used’ is selected. If any of the inputs is selected the generator torque limit is scaled
between zero and parameter generator torque limit.
0 = Not used
1 = AI1
2 = AI2
3 = AI3
4 = AI4
5 = FB Limit Scaling ID46 Monitoring value
Code
ID
Parameter
Notes
P1.6.3.9.1
610
Torque limit control P-gain “TorqLimCtrl P”
This parameter defines the gain of the torque limit controller. It is used in Open Loop
control mode only.
P1.6.3.9.2
611
Torque limit control I-gain “TorqLimCtrl I”
This parameter determines the I-gain of the torque limit controller. It is used in Open
Loop control mode only.0 = Not used
5.6.3.4 Open loop settings only
Code
ID
Parameter
Notes
P1.6.3.10.1
1382
Speed control output limit “SPC out limit”
Torque limit for the speed controller. It affects both the positive and negative direction
torques.
P1.6.3.10.2
646
Speed control positive limit “SPC pos limit”
Positive torque limit for speed controller output.
P1.6.3.10.3
645
Speed control negative limit “SPC Neg limit”
Negative torque limit for speed controller output.