73
SPX advanced – description of parameters
SPX ADVANCED APPLICATION MANUAL
SVCH0203—October 2017 www.eaton.com
Code
ID
Parameter
Notes
P1.4.4.3
325
1 “4-20 mA
Signal input ranges: 4 – 20 mA and 2 – 10 V
Input signal is used from 20 % to 100 %
Reference [Hz]
Max Freq
Min Freq
0 %
20 %
Analogue Input
100 %
2 “–10 - + 10 V
Signal input range: -10 V - + 10 V.
Input signal is used from -100 % to +100 %.
Reference
- Max Freq
Max Freq
0 V
-10 V
+10 V
Analogue Input
3 “Custom Range”
With custom range it is possible to freely adjust what input level corresponds to the
minimum and maximum frequencies..
Reference [Hz]
Analogue
Input
100 %
0 %
Min Freq
Max Freq
40 %
Custom
Min
80 %
Custom
Max