12
SPX Advanced application – monitoring values
SPX ADVANCED APPLICATION MANUAL
SVCH0203—October 2017 www.eaton.com
DIN StatusWord 1
DIN StatusWord 2
b11
DIN: B.6
DIN: E.4
b12
DIN: C.1
DIN: E.5
b13
DIN: C.2
DIN: E.6
b14
DIN: C.3
b15
DIN: C.4
V7.25.17
MC Status
ID 64
This is the value that is also send to fieldbus on
those fieldbus that do not use own state machine.
Motor control status word
False
True
b0
Not in ready state
Ready
b1
Not running
Running
b2
Direction clockwise
Counterclockwise
b3
No fault
Fault
b4
No warning
Warning
b5
At reference speed
b6
At Zero Speed
b7
Flux Ready
b8
TC Speed limiter active
b9
Encoder direction
Counterclockwise
b10
Under voltage fast stop
b11
No DC brake
DC Brake is active
b12
b13
Restart delay active
b14
b15
V7.25.18
Warning
ID 74
Last active warning.
V7.25.19
Shaft rounds
ID 1170
Rounds information from incremental encoder.
The value is reset when 24 Vdc is removed
from the drive.
V7.25.20
Shaft angle
ID 1169
Angle information from incremental encoder.
The value is reset when 24 Vdc is removed
from the drive.
V7.25.21
Fault word 10
ID 1202
Fault word 10 ID1202
Fault
Comment
b0
Speed error
F61
b1
b2
Over load fault active
F82
b3
No motor fault
F83
b4
PT100 Fault
F56 & F65
b5
b6
b7
b8
b9
b10
Fault word 10 ID1202
Fault
Comment
b11
b12
b13
b14
b15
V7.25.22
Warning word 10
ID 1269
Warning word 1 ID1269
Fault
Comment
b0
Speed error
W61
b1
Earth fault warning
W3
b2
Over load warning active
W82
b3
No motor warning
W83
b4
PT100 Warning
W56 & W65
b5
b6
b7
b8
b9
b10
b11
b12
b13
b14
b15
3.2.3 Master/Follower
Here are gathered relevant signals in Mater follower system.
otee:
N
Note for DriveSynch Systems:
In a DriveSynch system, only Master drive monitoring
signals are reliable.
Only directly measured values are reliable in follower units.
Even the Output Frequency of DriveSynch follower is not
directly observed and thus may not show actual output
frequency that is controlled by DriveSynch Master Drive.
V7.26.1
SB SystemStatus
ID 1601
D1: Status of all (max 4) drives status in
system bus.
D2, D3 and D4: Drive own status B0-B3
System bus status word ID1601
False
True
b0
Drive 1 in synch
b1
Drive 1 ready
b2
Drive 1 running
b3
Drive 1 fault
b4
Drive 2 in synch
b5
Drive 2 ready
b6
Drive 2 running
b7
Drive 2 fault
b8
Drive 3 in synch
b9
Drive 3 ready