20
SPX Advanced application – parameter list
SPX ADVANCED APPLICATION MANUAL
SVCH0203—October 2017 www.eaton.com
4.4 Input signals
4.4.1 Basic settings
Table 5 . Input signalse: basic settings . G1 .4 .1
Code
Parameter
Min
Max
Unit
Default
ID
Note
P1.4.1.1
Start/Stop logic selection
0
7
0
300
Start signal 1
(Default: DIN1)
Start signal 2
(Default: DIN2)
0
1
2
3
4
5
6
7
Start fwd
Start/Stop
Start/Stop
Start pulse
Start
Start fwd*
Start*/Stop
Start*/Stop
Start rvs
Reverse
Run enable
Stop pulse
Mot.Pot UP
Start rvs*
Reverse
Run enable
* = Rising edge required to
4.4.2 Digital inputs
Table 6 . Digital input signals, G1 .4 .2
Code
Parameter
Min
Default
ID
Note
P1.4.2.1
Start signal 1
0.1
A.1
403
Forward, See ID300
P1.4.2.2
Start signal 2
0.1
A.2
404
Reverse. See ID300
P1.4.2.3
Run enable
0.1
0.2
407
Motor start enabled (cc)
P1.4.2.4
Reverse
0.1
0.1
412
Direction forward (oc)
Direction reverse (cc)
P1.4.2.5
Preset speed 1
0.1
0.1
419
See preset speeds in basing parameter group G2.1
P1.4.2.6
Preset speed 2
0.1
0.1
420
P1.4.2.7
Preset speed 3
0.1
0.1
421
P1.4.2.8
Motor potentiometer reference DOWN 0.1
0.1
417
Mot.pot. reference decreases (cc)
P1.4.2.9
Motor potentiometer reference UP
0.1
0.1
418
Mot.pot. reference increases (cc)
P1.4.2.10 Fault reset
0.1
0.1
414
All faults reset (cc)
P1.4.2.11 External fault (close)
0.1
A.5
405
Ext. fault displayed (cc)
P1.4.2.12 External fault (open)
0.1
0.2
406
Ext. fault displayed (oc)
P1.4.2.13 Acc/Dec time selection
0.1
0.1
408
Acc/Dec time 1 (oc)
Acc/Dec time 2 (cc)
P1.4.2.14 Acc/Dec prohibit
0.1
0.1
415
Acc/Dec prohibited (cc)
P1.4.2.15 DC braking
0.1
0.1
416
DC braking active (cc)
P1.4.2.16 Jogging speed
0.1
A.4
413
Jogging speed selected for frequency reference (cc)
P1.4.2.17 Remote 1 ref 1/2 selection
0.1
0.1
422
IO reference selection:14 ID117
P1.4.2.18 Force Local
0.1
0.1
410
Force control place to Local (cc)
P1.4.2.19 Force Remote 1
0.1
A.6
409
Force control place to Remote 1 (cc)
P1.4.2.20 Force Remote 2
0.1
0.1
411
Force control place to Remote 2 (cc)
P1.4.2.21 Parameter set 1/set 2 selection
0.1
0.1
496
Closed cont.=Set 2 is used
Open cont.=Set 1 is used
P1.4.2.22 Motor control mode 1/2
0.1
0.1
164
Closed cont.=Mode 2 is used
Open cont.=Mode 1 is used
See par 2.6.1, 2.6.12
P1.4.2.23 External brake acknowledge
0.1
0.2
1210
Monitoring signal from mechanical brake
P1.4.2.24 Cooling monitor
0.1
0.2
750
Used when water cooled unit
P1.4.2.25 Enable inching
0.1
0.1
532
Enables inching function
P1.4.2.26 Inching 1
0.1
0.1
530
Inching reference 1 (default forward 2 Hz.
See P1.4.16). This will start the drive.