94
Commander SE Advanced User Guide
Issue Number: 4
3.13 Menu 14: PID control
Parameter
Range
Type
Default
Setting
Update
Rate
14.01 PID controller output
±
100%
RO
Bi
P
L3
14.02 Main reference source
0.00 ~ 21.51
Menu.Parameter
RW
Uni P
0.00
B
14.03 PID reference source parameter
0.00 ~ 21.51
Menu.Parameter
RW
Uni
P
0.00 B
14.04 PID feedback source parameter
0.00 ~ 21.51
Menu.Parameter
RW
Uni
P
0.00 B
14.05 PID reference invert
0 or 1
RW
Bit
0
L3
14.06 PID feedback source invert
0 or 1
RW
Bit
0
L3
14.07 PID reference slew rate limit
0 ~ 3200.0 secs
RW
Uni
0.0
B
14.08 PID enable
0 or 1
RW
Bit
0
L3
14.09
Optional PID enable source
parameter
0.00 ~ 21.51
Menu.Parameter
RW
Uni
P
0.00 B
14.10 PID proportional gain
0 ~ 2.50
RW
Uni
1.00
L3
14.11 PID integral gain
0 ~ 2.50
RW
Uni
0.50
L3
14.12 PID derivative gain
0 ~ 2.50
RW
Uni
0.00
L3
14.13 PID output high limit
0 ~ 100.0%
RW
Uni
100.0
L3
14.14 PID output low limit
±
100%
RW
Bi
-100.0 L3
14.15 PID output scale factor
0.000 ~ 2.50
RW
Uni
1.00
L3
14.16 PID output destination
0.00 ~ 21.51
Menu.Parameter
RW
Uni
R
P
0.00 I
14.17 PID hold integrator enable
0 or 1
RW
Bit
0
L3
14.18 PID symmetrical limits enable
0 or 1
RW
Bit
0
L3
14.19 PID main reference
±
100.0%
RO
Bi
P
L3
14.20 PID reference
±
100.0%
RO Bi
P
L3
14.21 PID feedback
±
100.0%
RO
Bi
P
L3
14.22 PID error
±
100.0%
RO
Bi
P
L3
Содержание COMMANDER SE
Страница 76: ...76 Commander SE Advanced User Guide Issue Number 4...
Страница 93: ...Commander SE Advanced User Guide 93 Issue Number 4...
Страница 98: ...98 Commander SE Advanced User Guide Issue Number 4...
Страница 142: ...142 Commander SE Advanced User Guide Issue Number 4 Figure 6 9 Input line reactor 4400 0241 All dimensions in mm...
Страница 144: ...144 Commander SE Advanced User Guide Issue Number 4 Figure 7 3 Commander SE Size 4 All dimensions in mm...