112
Commander SE Advanced User Guide
Issue Number: 4
The total current available from the +24V rail, which includes the digital output, is 100mA. Therefore if the digital
output is providing 30mA, the +24V rail will only provide 70mA.
If the enable terminal is opened, the drive’s output is disabled and the motor will coast to a stop. The drive cannot be re-
enabled for 2 seconds following the opening of the enable terminal.
† Following a drive trip, open and close the Enable terminal to reset the drive. If the Run Forward or Run Reverse
terminal is closed, the drive will run straight away.
* Following a drive trip and a reset via the Stop/Reset key the Run Forward or Run Reverse terminals will need to be
opened and closed to allow the drive to run. This ensures that the drive does not start when the Stop/Reset key is
pressed.
There is a delay of 65ms in the drives software when switching from Run Forward to Run Reverse or vice-versa. The
delay is to allow the direction of motor rotation to be changed without the drive entering the selected stopping
mode, e.g. coast to stop.
If the Commander SE is being used on an application where the terminal timing is critical, the terminal set-up mode
should be changed as to remove this 65ms delay. This can be done by setting Parameter 35 to mode 2 or 3 so that
the terminals are set up as Run/Stop terminals and not Run Forward/Run Reverse terminals.
6
Analog voltage output
Default
Motor Speed (See parameter 36)
Absolute maximum voltage range
+35V to -1V with respect to 0V common
Voltage range
0 to +10V
Scaling: Motor speed output
0V represent 0Hz/0 rpm output
+10V represents the value of parameter
02
,
Maximum speed.
% Motor load output
Maximum output current
5mA
Resolution
0.1% (10 bit)
Accuracy
±
5%
Update time
22ms
Protection
tolerates continuous short circuit to 0V
7
+24V output
Voltage accuracy
±
10%
Maximum output current
100mA
Protection
tolerates continuous short circuit to 0V
8
Digital output
Function
Zero Speed Output
Absolute maximum voltage range
+35V to -1V with respect to 0V common
Voltage range
0V to +24V
Maximum output current
50mA at +24V
Output impedance
10k
Ω
pull-down resistor in inactive state.
Update time
1.5ms
Operation of digital output
+24V = Zero speed, 0V = Above zero speed
9
10
11
12
13
Digital input - Enable / Reset
†
Digital input - Run Forward (Edge triggered) *
Digital input - Run Reverse (Edge triggered) *
Digital input - Local/Remote Speed Ref (A1/A2)
Digital input - Jog
Default
Positive logic (See parameter 34)
Voltage range
0V to +24V
Absolute maximum voltage range
+35V to -18V with respect to 0V common
Nominal threshold voltage
+10V
Input impedance
7.5k
Ω
Sample time
1.5ms
V
OUT
Active Current
1.5
Drive Rated Current
×
------------------------------------------------------------------------------------
10
×
=
NOTE
NOTE
Содержание COMMANDER SE
Страница 76: ...76 Commander SE Advanced User Guide Issue Number 4...
Страница 93: ...Commander SE Advanced User Guide 93 Issue Number 4...
Страница 98: ...98 Commander SE Advanced User Guide Issue Number 4...
Страница 142: ...142 Commander SE Advanced User Guide Issue Number 4 Figure 6 9 Input line reactor 4400 0241 All dimensions in mm...
Страница 144: ...144 Commander SE Advanced User Guide Issue Number 4 Figure 7 3 Commander SE Size 4 All dimensions in mm...