Commander SE Advanced User Guide
109
Issue Number: 4
Figure 4-6 Commander SE size 5 power circuit layout
Figure 4-7 Method of powering up the Commander SE size 5 by the DC bus using the drives internal inrush resistor
The source of the relay must NOT be changed from Drive Healthy. For relay ratings refer to the Commander SE User
Guide.
4.3 Gland plate holes
A slot has been provided in the gland plate of sizes 1 to 4 for control cables. One of the gland plate holes can be used for
control cables but this should be separate from any power cables.
Size 5 has a separate gland plate with two 22mm holes for the control cables.
Table 4-1 Gland plate hole dimensions
Motor
+DC bus
-DC bus
L1
L2
L3
U
V
W
+
-
DC Supply with each
drive individually fused
NC
NO
Soft start
contactor
110V ac supply for soft
start contactor coil
Contactor coil supply
must be wired through
the drive healthy relay
Terminal 15
Terminal 16
Contactor
coil
DC Choke
NO
Normally Open Auxiliary
contact must be hard
wired with the drive
enable on terminal 9
NOTE
Drive size
Number of holes in power terminal gland plate
22mm
27mm
1
3
2
3
3
1
2
4
2
2
5
11
Содержание COMMANDER SE
Страница 76: ...76 Commander SE Advanced User Guide Issue Number 4...
Страница 93: ...Commander SE Advanced User Guide 93 Issue Number 4...
Страница 98: ...98 Commander SE Advanced User Guide Issue Number 4...
Страница 142: ...142 Commander SE Advanced User Guide Issue Number 4 Figure 6 9 Input line reactor 4400 0241 All dimensions in mm...
Страница 144: ...144 Commander SE Advanced User Guide Issue Number 4 Figure 7 3 Commander SE Size 4 All dimensions in mm...