Commander SE Advanced User Guide
181
Issue Number: 4
Drive set-up
Parameter set-up
Firstly, establish the actual speed in Hz that is needed to maintain the required pressure for the system. This should be
set by the potentiometer or terminal 2 or by the value in preset speed
1.22
. This will be the speed set point.
On terminal 2, 0 - 10V = 0 - 100%
Parameter 1.22, 0 - 1000 = 0 - 100%
Set
7.10
= 0.00
Analog input 1 is not required to be assigned to a destination.
Set
7.14
= 0.00
Analog input 2 is not required to be assigned to a destination.
Set
7.11
for the appropriate feedback range.
Set
14.03
=
7.01
or
1.22
dependant on the chosen speed and set point.
Set
14.04
=
7.02
PID feedback reference assigned to feedback signal from current transducer.
Set
14.08
= 1
Enable PID.
Set
14.16
=
1.36
PID output assigned to control the final speed reference, which will increase or decrease
automatically depending on the errordetected and therefore maintain a constant pressure.
It may be necessary to adjust the internal PID gains
14.10
,
14.11
and
14.12
to improve system stability and response.
Perform a Save routine:
xx.00
= 1000 and press red Stop / Reset button on drive.
With this set-up, as the feedback signal increases the speed of the motor will decrease and vice versa.
For level control and temperature control, as the feedback signal increases the speed of the motor should increase. To
achieve this, set
14.06
= 1 and
14.05
= 1 to invert the feedback signal.
Terminal 2
7.01
+10V
0V
1.22
14.03
X-1
0
1
1.36
X-1
1
0
14.04
7.02
Terminal 5
Mode
7.11
T
Set point
PID loop
Feedback
Speed
reference
NOTE
Содержание COMMANDER SE
Страница 76: ...76 Commander SE Advanced User Guide Issue Number 4...
Страница 93: ...Commander SE Advanced User Guide 93 Issue Number 4...
Страница 98: ...98 Commander SE Advanced User Guide Issue Number 4...
Страница 142: ...142 Commander SE Advanced User Guide Issue Number 4 Figure 6 9 Input line reactor 4400 0241 All dimensions in mm...
Страница 144: ...144 Commander SE Advanced User Guide Issue Number 4 Figure 7 3 Commander SE Size 4 All dimensions in mm...