Commander SE Advanced User Guide
179
Issue Number: 4
12.19 Programmable threshold set-up
The Commander SE drive software supports a software controllable numerical comparator. This comparator can be used to
detect when an internal or external signal exceeds a user set point threshold. The threshold comparator also provides a
hysteresis band to prevent erratic operation at or near the threshold point.
This example shows how the programmable threshold can be set up to switch on an integrated motor cooling fan, when the
drive speed falls below 50%.
Parameter set-up
12.03
=
5.01
Threshold detector source parameter assigned to motor frequency.
12.04
= 50% Threshold level as a percentage of maximum reference.
8.27
=
12.01
Programmable relay source parameter assigned to “threshold exceeded” signal.
Set threshold detector hysteresis band (
12.05
) if required. This will define the band within which no change will occur on
the output.
Perform a Save routine:
xx.00
= 1000 and press red Stop / Reset button on drive.
U V W
1 2 3
16
15
SPEED REFERENCE
Motor ventilation ON
Motor ventilation OFF
100%
50%
0%
240V AC
Fan Supply
Contactor
Содержание COMMANDER SE
Страница 76: ...76 Commander SE Advanced User Guide Issue Number 4...
Страница 93: ...Commander SE Advanced User Guide 93 Issue Number 4...
Страница 98: ...98 Commander SE Advanced User Guide Issue Number 4...
Страница 142: ...142 Commander SE Advanced User Guide Issue Number 4 Figure 6 9 Input line reactor 4400 0241 All dimensions in mm...
Страница 144: ...144 Commander SE Advanced User Guide Issue Number 4 Figure 7 3 Commander SE Size 4 All dimensions in mm...