82
Commander SE Advanced User Guide
Issue Number: 4
If this flag is set to 1 then the drive will trip (Et). An inversion of the input logic must also be programmed such that the
terminal must be active to prevent a trip.
Although this parameter is defined as Read Only, it can be programmed as a destination for a digital input. It cannot be
written to over serial communications.
A 0 - 1 change on this parameter will cause a drive reset. If a drive reset terminal is required on the drive the required terminal
must be programmed to control this bit.
If this parameter is set to zero then no auto reset will ever occur. Any other value will cause the drive to automatically reset
following a trip for the number of times programmed. Parameter
10.35
defines the time between the trip and the auto reset.
The reset count is only incremented when the trip is the same as the previous trip, otherwise it is reset to 0. When the reset
count reaches the programmed value, any further trip of the same value will not incur an auto-reset.
If there has been no trip for 2 minutes then the reset count is cleared.
Auto reset will not occur on an External trip (Et).
This parameter defines the time between a trip and an auto reset subject to the minimum trip time for IGBT overcurrent trips.
If this parameter is 0 then parameter
10.01
(Drive healthy) is cleared every time the drive trips regardless of any auto-reset
that may occur. When this parameter is set the Inverter healthy indication is not cleared on a trip if an auto-reset is going to
occur.
If this parameter is set, the drive will stop before tripping on non important trips. Non important trips are cL, EEF error when
saving data, O.Ld, and PH.
10.32
External trip
Ú
0 or 1
Ö
RO
Bit
10.33
Drive reset
Ú
0 or 1
Ö
0
RW
Bit
10.34
No. of auto reset attempts
Ú
0 ~ 5
Ö
0
RW
Uni
10.35
Auto reset time delay
Ú
0 ~ 25.0
Ö
1.0
s
RW
Uni
10.36
Hold drive healthy until last auto-reset attempt
Ú
0 or 1
Ö
0
RW
Bit
10.37
Stop drive on non important trips
Ú
0 or 1
Ö
0
RW
Bit
0
100
Overload
accumulator%
t
10.30
10.31
10.39
Содержание COMMANDER SE
Страница 76: ...76 Commander SE Advanced User Guide Issue Number 4...
Страница 93: ...Commander SE Advanced User Guide 93 Issue Number 4...
Страница 98: ...98 Commander SE Advanced User Guide Issue Number 4...
Страница 142: ...142 Commander SE Advanced User Guide Issue Number 4 Figure 6 9 Input line reactor 4400 0241 All dimensions in mm...
Страница 144: ...144 Commander SE Advanced User Guide Issue Number 4 Figure 7 3 Commander SE Size 4 All dimensions in mm...