Commander SE Advanced User Guide
59
Issue Number: 4
Parameter 6.42 - further information
This parameter provides a means of disabling the use of the control word and control mask, parameters
6.41
and
6.42
, and
returning start/stop functionality to terminals 9,10 and 11.
Parameter
6.43
must be set to 1 to allow control of the drive via the control word. If this is not set to 1, then these parameters
will not do anything. (
6.43
must be set back to 0 for terminal control.)
Binary Code
Bit Position
Parameter 6.42
Function
Parameter 6.41 Mask
Bit Number
1
0
Drive Enable
Mask bit 0
2
1
Run Forward
Mask bit 1
4
2
Jog
Mask bit 2
8
3
Run Reverse
Mask bit 3
16
4
Forward / Reverse
Mask bit 4
32
5
Run
Mask bit 5
64
6
Not Stop
Mask bit 6
128
7
Reserved
Reserved
256
8
Reserved
Reserved
512
9
Reserved
Reserved
1024
10
Reserved
Reserved
2048
11
Reserved
Reserved
4096
12
Reserved
Reserved
8192
13
Reserved
Reserved
16384
14
Watchdog Update
Watchdog Enable
6.43
Control word enable
Ú
0 or 1
Ö
0
RW
Bit
Содержание COMMANDER SE
Страница 76: ...76 Commander SE Advanced User Guide Issue Number 4...
Страница 93: ...Commander SE Advanced User Guide 93 Issue Number 4...
Страница 98: ...98 Commander SE Advanced User Guide Issue Number 4...
Страница 142: ...142 Commander SE Advanced User Guide Issue Number 4 Figure 6 9 Input line reactor 4400 0241 All dimensions in mm...
Страница 144: ...144 Commander SE Advanced User Guide Issue Number 4 Figure 7 3 Commander SE Size 4 All dimensions in mm...