84
Commander SE Advanced User Guide
Issue Number: 4
3.11 Menu 11: Miscellaneous
Parameter
Range
Type
Default
Setting
Update Rate
11.01~
11.20
Not used
11.21
Parameter scaling
0.00 ~ 99.99
RW
Uni
1.00
B
11.22
Parameter displayed at power up
select
0 or 1
RW
Bit
0
B
11.23
Serial comms address
0.0 ~ 24.7
Group.Unit
RW
Uni
1.1 BF
11.24
Serial comms mode
(0) Ansi
(1) rtu
(2) F.bus
RW
Txt
R
0 BF,
L1
11.25
Serial comms baud rate
(0) 2.4
(1) 4.8
(2) 9.6
(3) 19.2
RW
Txt
(1)4.8 BF
11.26
Serial comms minimum transmit
delay
0-250mS
RW
Uni
20 BF,
L1
11.27~
11.28
Not used
11.29
Drive software version
1.00 ~ 9.99
RO
Uni
P
I
11.30
User security code
0 ~ 9999
RW
Uni
S
P
0
B
11.31
Not used
11.32
Drive rated continuous current
1.50 ~ 70.0A
RO
Uni
P
I
11.33
Drive voltage rating
240 ~ 480V
RO
Uni
P
I
11.34
Drive software sub version
0 ~ 99
RO
Uni
P
I
11.35
Drive DSP software version
0 ~ 9.9
RO
Uni
P
B
11.36~
11.40
Not used
11.41
Status mode timeout
0 ~ 250secs
RW
Uni
P
240
B
11.42
Parameter cloning
(0) no
(1) rEAD
(2) Prog
(3) Auto
(4) boot
RW
Uni
Txt
R
(0)no B
11.43
Load default parameters
(0) no
(1) Eur
(2) USA
(3) br.Eu
(4) br.US
RW
Uni
Txt
R
(0)no B
11.44
Security status
(0) L1
(1) L2
(2) Loc
RW
Uni
Txt
R
(0)L1
B
11.45
Select motor 2 parameters
0 or 1
RW
Bit
0
B
Содержание COMMANDER SE
Страница 76: ...76 Commander SE Advanced User Guide Issue Number 4...
Страница 93: ...Commander SE Advanced User Guide 93 Issue Number 4...
Страница 98: ...98 Commander SE Advanced User Guide Issue Number 4...
Страница 142: ...142 Commander SE Advanced User Guide Issue Number 4 Figure 6 9 Input line reactor 4400 0241 All dimensions in mm...
Страница 144: ...144 Commander SE Advanced User Guide Issue Number 4 Figure 7 3 Commander SE Size 4 All dimensions in mm...