12.7 Drive set-up for 8 preset speeds
Parameter set up
8.39
= 1
(disable auto set-up of terminals 12 and 13).
6.04
= 4
(allow terminals 9,10 and 11 to be programmed).
Perform a Save routine:
xx.00
= 1000 and press red Stop / Reset button on the drive
8.26
= 1.47 (Terminal 13).
8.25
= 1.46 (Terminal 12).
8.24
= 1.45 (Terminal 11).
1.14
to Pr, Mode 3 (allows the above terminals to control preset speeds).
1.21
= ?
(required preset speed 1).
1.22
= ?
(required preset speed 2).
1.23
= ?
(required preset speed 3).
1.24
= ?
(required preset speed 4).
1.25
= ?
(required preset speed 5).
1.26
= ?
(required preset speed 6).
1.27
= ?
(required preset speed 7).
1.28
= ?
(required preset speed 8).
Perform a Save routine:
xx.00
= 1000 and press red Stop / Reset button on the drive
If a negative value speed is required then set parameter
1.10
= 1 (Enable negative preset speeds).
0 = Switch open
1 = Switch closed
The relative preset speed will be selected according to the sequence of switch settings on terminals 11, 12 and 13.
Terminals 9 (Enable) and 10 (Run Forward) will need to be connected to +24V for the drive to run.
12.8 Utilising dual motor set-up
The Commander SE has the ability to control 2 different motors of different ratings, so long as they are both within the
specification of the drive. Only one motor can be controlled at any one time. The motor 2 parameters should be entered in
Menu 21.
A digital input should be programmed to
11.45
to select the second motor map. The second motor map will only be
implemented when the drive is in the inhibit, ready or tripped modes.
A parameter in Menu 21,
21.15
, will change from a 0 to a 1 when the second motor map is implemented. This can be used to
change a changeover relay which intern will select the correct motor contactor.
See diagram on the next page.
Parameter set-up
8.39
= 1
Disable automatic set-up of terminals 12 and 13
8.26
=
11.45
Terminal 13 to select second motor map.
8.21
=
21.15
Digital output to second motor map implemented
Perform a Save routine:
xx.00
= 1000 and press red Stop / Reset button on the drive
Enter motor 1 nameplate details into motor map parameters in level 1 or Menu 5 with motor 1 selected and perform an
autotune (
0.38
= 1[non rotating] or 2 [rotating])
Enter motor 2 nameplate details into motor map 2 in Menu 21 and with motor 2 selected perform an autotune (
0.38
= 1[non
rotating] or 2 [rotating])
Operation
When the switch on terminal 13 is open, the external relay will be de-energised and therefore the contactor to motor 1 will be
closed.
If the drive is running and the switch on terminal 13 is closed, the contactor to motor 1 will remain closed. If the drive is
stopped or disabled, the external relay will energise and open the contactor to motor 1 and close the contactor to motor 2.
This set-up ensures that the drive is disabled when the contactors are opened or closed.
Terminal 13
Terminal 12
Terminal 11
Preset Speed
0
0
0
1
0
0
1
2
0
1
0
3
0
1
1
4
1
0
0
5
1
0
1
6
1
1
0
7
1
1
1
8
Содержание COMMANDER SE
Страница 76: ...76 Commander SE Advanced User Guide Issue Number 4...
Страница 93: ...Commander SE Advanced User Guide 93 Issue Number 4...
Страница 98: ...98 Commander SE Advanced User Guide Issue Number 4...
Страница 142: ...142 Commander SE Advanced User Guide Issue Number 4 Figure 6 9 Input line reactor 4400 0241 All dimensions in mm...
Страница 144: ...144 Commander SE Advanced User Guide Issue Number 4 Figure 7 3 Commander SE Size 4 All dimensions in mm...