Commander SE Advanced User Guide
9
Issue Number: 4
Table 1-1 RS Components Part Numbers
The instructions provided are only applicable for Stewart manufactured RJ45 connectors.
1.2 Serial communications connections
If more than one drive is to be connected to a serial link, make connections as shown in the diagram below.
•
The serial communications cable must be shielded. The shield(s) must be connected as shown in the diagram below:
A data communications cable should not run parallel to any power cables, especially ones that connect drives to
motors. If parallel runs are unavoidable, ensure a minimum spacing of 300mm (12 in.) between the communications
cable and the power cable.
Cables crossing one another at right-angles are unlikely to give trouble. The maximum cable run length for a EIA485
link is 1,200 metres (4,000 feet).
If more than one drive is connected to the host computer, please adjust the serial address of each drive to ensure that each
drive has a unique address.
Therefore with the drive in the above condition, all commissioning and operation can be done using the EIA485
communication link.
T-Bar connector / splitter from Insight.
Part No: CNX3A02KNW
www.insight.com
Pin 6 TX Enable
The TX Enable pin is a 0 to 5V output from the Drive that can be used to externally control and switch the buffers on a serial
communications converter from transmit to receive and vice-versa. An example of a converter that can be used with this
signal is the Amplicon 485Fi.
Description
Part Number
Stewart RJ45 Connectors
290-4780
Ferrule Crimp Hand tool
290-4853
5.2mm Cable Crimp
290-4875
4.5mm Cable Crimp
290-4869
RJ45 Hand tool
290-4796
Shielded Die
290-4847
Unshielded Die
290-4825
NOTE
NOTE
1
2
3
4
5
6
7
8
RJ45
RJ45 T-BAR
CONNECTOR
SYSTEM
CONTROLLER
(RS485)
TRANSCEIVER
Tx / Rx
Tx / Rx
Drive 1
Drive 2
RJ45 CONNECTOR
PIN 1 TERMINATION
RESISTOR
PIN 2 Rx Tx
PIN 3 0V
PIN 4 +26V
PIN 5 NOT USED
PIN 6 TX ENABLE
PIN 7 Rx Tx
PIN 8 LINKED TO PIN 7
1
2
3
4
5
6
7
8
RJ45
1
14
1
14
0V
Tx / Rx
Tx / Rx
Содержание COMMANDER SE
Страница 76: ...76 Commander SE Advanced User Guide Issue Number 4...
Страница 93: ...Commander SE Advanced User Guide 93 Issue Number 4...
Страница 98: ...98 Commander SE Advanced User Guide Issue Number 4...
Страница 142: ...142 Commander SE Advanced User Guide Issue Number 4 Figure 6 9 Input line reactor 4400 0241 All dimensions in mm...
Страница 144: ...144 Commander SE Advanced User Guide Issue Number 4 Figure 7 3 Commander SE Size 4 All dimensions in mm...