182
Commander SE Advanced User Guide
Issue Number: 4
12.21 2 x Latching Run Forward Inputs
Set-up for 2 x Latching Run Forward Inputs
V01.08.00 software or later must be used for this set-up. It will not work with earlier versions.
The following set-up gives two momentary latching Run Forward inputs with two different speeds set by the analog inputs.
Set-up
6.04
= 1
Perform a Save routine:
xx.00
= 1000 and press red Stop / Reset button on the drive
1.10
= 1
Allow negative digital references
1.22
= 0.2
Preset 2 to 0.2
1.23
= 0.1
Preset 3 to 0.1
7.13
= 1
Analog input 2 invert
9.04
=
1.12
Logic function source 1 to reverse selected bit
9.10
=
12.10
Logic function destination to variable select selector bit
12.08
=
1.23
Variable selector source 1 to preset 3
12.09
=
1.22
Variable selector source 2 to preset 2
12.11
=
1.14
Variable selector destination to reference selector
Perform a Save routine:
xx.00
= 1000 and press red Stop / Reset button on the drive
Terminal set-up
Operation
When the Run Forward 1 terminal is closed momentarily the drive will run forward at the speed requested by analog input 1
When the Run Forward 2 terminal is closed momentarily the drive will run forward at the speed requested by analog input 2
NOTE
2
7
8
9
10
11
+24V
/Stop
Run Forward 1
Run Forward 2
6
5
4
3
1
Analog input 2
Analog input 1
0V
+10V
mA Input
Содержание COMMANDER SE
Страница 76: ...76 Commander SE Advanced User Guide Issue Number 4...
Страница 93: ...Commander SE Advanced User Guide 93 Issue Number 4...
Страница 98: ...98 Commander SE Advanced User Guide Issue Number 4...
Страница 142: ...142 Commander SE Advanced User Guide Issue Number 4 Figure 6 9 Input line reactor 4400 0241 All dimensions in mm...
Страница 144: ...144 Commander SE Advanced User Guide Issue Number 4 Figure 7 3 Commander SE Size 4 All dimensions in mm...