Commander SE Advanced User Guide
163
Issue Number: 4
12.5 Drive overload alarm signal connection
The digital output or the status relay can be set-up to signal an alarm output such as drive temperature alarm 'hot', drive
overload alarm 'OVL' or braking resistor overload 'br.rS'.
Example 1
To provide a digital output signal when the drive goes into current overload.
Parameter settings
Set parameter
8.21
to parameter
10.17
Perform a Save routine:
xx.00
= 1000 and press red Stop / Reset button on the drive
Connections
Control signal terminal block
Operation
When the drive goes into current overload and OVL flashes on the display, terminal 8 will go to +24V and therefore light the
LED.
The signal from terminal 8 could be go to a PLC or other type of signal monitoring system.
Example 2
To provide a signal when the drive goes into current overload using the drives status relay.
Parameter settings
Set parameter
8.27
to parameter
10.17
Perform a Save routine:
xx.00
= 1000 and press red Stop / Reset button on the drive
Connections
Control signal terminal block
Operation
When the drive goes into current overload and OVL flashes on the display, the relay will close and therefore light the LED.
The signal from the +24V rail through the relay could be go to a PLC or other type of signal monitoring system.
12.6 Motor thermistor set up
Terminal 13 (digital input 6) can be used as a motor thermistor input. To set this up, set parameter
50
= ON. Connect the
motor thermistor between 0V (terminals 1 or 4) and terminal 13.
The trip resistance is approximately 3k and the reset resistance is approximately 1k8.
The input does not have Motor thermistor short circuit protection. Therefore if the motor thermistor goes short circuit, the drive
will not trip out on ‘th’. The motor thermistor going short circuit will not damage the drive.
There is not a parameter to display the motor temperature.
The motor thermistor can also be enabled through the advanced menus by setting parameter
8.40
= 1 and performing a save
by setting
xx.00
to 1000 and pressing the Stop/Reset button.
1
8
14
PLC
1
8
14
PLC
15 16
Содержание COMMANDER SE
Страница 76: ...76 Commander SE Advanced User Guide Issue Number 4...
Страница 93: ...Commander SE Advanced User Guide 93 Issue Number 4...
Страница 98: ...98 Commander SE Advanced User Guide Issue Number 4...
Страница 142: ...142 Commander SE Advanced User Guide Issue Number 4 Figure 6 9 Input line reactor 4400 0241 All dimensions in mm...
Страница 144: ...144 Commander SE Advanced User Guide Issue Number 4 Figure 7 3 Commander SE Size 4 All dimensions in mm...