Commander SE Advanced User Guide
175
Issue Number: 4
Figure 12-3 Terminal Connection Diagram
Operation
With the Enable terminal closed press the normally open Run switch to run the drive, the drive will run up to speed.
To stop the drive either
press the normally closed Stop switch in series with the connection between terminals 8 and 9. The motor will stop under
the control of selected stopping mode and then disable
or
open the enable switch to terminal 12. The drives output will be inhibited and the motor will coast to a stop.
When the drive is running and the motor current (
4.01
) is below the threshold level set in
12.04
, the drive will run normally. If
the motor current increases above this threshold, then the programmable threshold indicator (
12.01
) will be set to a 1. This
will cause the programmable logic timer (
9.09
) to start timing. Once this time has elapsed the programmable logic indicator
(
9.01
) will cause the digital output to change state. Because the digital output is feeding into the Not Stop terminal, the drive
will Stop.
If during the programmable logic timer period the motor current falls back below the programmable threshold level, the drive
will continue to run normally.
The programmable logic timer (
9.09
) and the programmable logic threshold level (
12.04
) can be set as required for the
particular application.
12.15 Keypad / Terminal Control
The set-up below allows the drive to be started and stopped from the drives terminals and for the speed of the motor to be
controlled by the keypads up and down buttons.
This set-up will only function with V01.08.00 (and later) Commander SE User Interface software.
Parameter set-up
Set
1.22
= 0.4
Preset speed reference 2 to 0.4
Set
1.23
= 0.1
Preset speed reference 3 to 0.1
Set
9.04
=
6.30
Prog. logic function 1 source parameter to run forward
Set
9.05
= 1
Prog. logic function source 1 invert inverted
Set
9.06
=
6.32
Prog. logic function 2 source parameter to run reverse
Set
9.07
= 1
Prog. logic function source 2 invert inverted
Set
9.10
=
12.10
Prog. logic function destination to variable selector select
Set
12.08
=
1.22
Variable selector source 1 to preset speed 1
Set
12.09
=
1.23
Variable selector source 2 to preset speed 2
Set
12.11
=
1.14
Variable selector destination to reference select
Perform a Save routine:
xx.00
= 1000 and press red Stop / Reset button on the drive.
Operation
When either the run forward or run reverse terminal is closed allowing the drive to run, keypad mode is selected. This allows
the drive’s speed to be increased or decreased via the drive’s up and down buttons on the drive’s keypad. The drive can also
be stopped or started via the drive’s keypad.
If the drive is running and either the run forward or run reverse terminal is opened, the drive will stop as keypad mode is
deselected and terminal mode selected.
Digital output
Not Stop
Run
Enable
+24V
8
9
10
11
12
13
14
Forward / Reverse
NOTE
Содержание COMMANDER SE
Страница 76: ...76 Commander SE Advanced User Guide Issue Number 4...
Страница 93: ...Commander SE Advanced User Guide 93 Issue Number 4...
Страница 98: ...98 Commander SE Advanced User Guide Issue Number 4...
Страница 142: ...142 Commander SE Advanced User Guide Issue Number 4 Figure 6 9 Input line reactor 4400 0241 All dimensions in mm...
Страница 144: ...144 Commander SE Advanced User Guide Issue Number 4 Figure 7 3 Commander SE Size 4 All dimensions in mm...