S e n d d o c u m e n t a t i o n c o m m e n t s t o m d s f e e d b a c k - d o c @ c i s c o . c o m
2-22
Cisco MDS 9000 Family Troubleshooting Guide, Release 3.x
OL-9285-05
Chapter 2 Troubleshooting Installs, Upgrades, and Reboots
Troubleshooting Cisco SAN-OS Software System Reboots
Usage for bootflash://sup-local
107465728 bytes used
78619648 bytes free
186085376 bytes total
Step 9
Load the system image from the bootflash: files system.
switch(boot)#
load bootflash:system-image1
Uncompressing system image: bootflash:/system-image1
CCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCCC
Would you like to enter the initial configuration mode? (yes/no):
yes
Note
If you enter
no
, you will return to the
switch#
login prompt, and you must manually configure
the switch.
Step 10
Log in to the switch using the password configured in
Step 9
.
switch login:
admin
Password:
Cisco Storage Area Networking Operating System (SAN-OS) Software
TAC support: http://www.cisco.com/tac
Copyright (c) 2002-2008, Cisco Systems, Inc. All rights reserved.
The copyrights to certain works contained herein are owned by
other third parties and are used and distributed under license.
Some parts of this software may be covered under the GNU Public
License or the GNU Lesser General Public License. A copy of
each such license is available at
http://www.gnu.org/licenses/gpl.html and
http://www.gnu.org/licenses/lgpl.html
switch#
Step 11
Configure the boot variable.
switch #
config t
switch(config)#
boot kickstart bootflash:kickstart-image1
switch(config)#
boot system bootflash:system-image1
switch(config)#
end
switch#
Step 12
Save the configuration.
switch#
copy running-config startup-config
[########################################] 100%
switch#
Recovery for Switches with Dual Supervisor Modules
This section describes how to recover when one or both supervisor modules in a dual supervisor switch
have corrupted bootflash.