4.
Move to the
Connection
tab.
Now configure the EtherNet/IP cycle time (4 ms
is advisable) in which data is to be transmitted.
The shortest period supported by Vision Sensor
is 4 ms.
Shorter periods reduce the Vision Sensor's
computing power available for feature checking
and
thus it evaluation performance.
Longer periods increase the time taken for
evaluation
of received data and sending result data and
thus reduce response performance.
The period you choose will therefore be a
compromise between these factors.
5.
The project has to be loaded into the PLC to
test data transmission.
Switch the PLC to run mode.