Technical Documentation
VeriSens
®
v2.11.0-B4
334/429
Baumer Optronic GmbH
Radeberg, Germany
15.4.20 UJ command
– transfer a new job
This function enables you to transfer a new job to the device.
NOTE
The job name including the file extension ".app" can be a maximum of 31 characters.
NOTE
Jobs cannot be renamed on the PC when using the UJ command for job transfers.
Example
Structure of the command
PLC
device
Command
Parameters
U
J
0
0
0
3
0
0
0
4
F
9
E
2
…
U
pdate
J
ob
4 byte ASCII hex
job number
8 byte ASCII hex
Job size
Job as binary data
Structure of the Response
PLC
device
Response
R
U
0
0
R
esponse
U
pdate
00 = received OK
01 = device not in Configuration mode
02 = invalid job number
03 = job could not be loaded
04 = job update still active
05 = invalid network settings
06 = invalid device name
07 = backup file device type not identical to the device
08 = user management is active
09 = device file is password protected
10 = file could not be opened for writing
11 = file write error
12 = incompatible backup
13 = only the firmware cannot be imported
FA = Receipt timeout
NOTE
Timeout adjustable in the
Application Suite
under:
Device
Device settings
Process interface
other = internal fault