Technical Documentation
VeriSens
®
v2.11.0-B4
314/429
Baumer Optronic GmbH
Radeberg, Germany
15.4.7 GI command
– access an image (only via Ethernet)
This function enables you to access live images and defect images with and without the field of view.
Example
Structure of the command
PLC
device
Command
Parameters
G
I
0
0
0
0
G
et
I
mage
2 byte ASCII hex
00 = live image
01 = Live image with
field of view
80 = Fault image
81 = Fault image with
field of view
2 byte ASCII hex
image number
00 = Last image,
01 = penultimate image,
02 = …
Structure of the Response
PLC
device
Response
R
I
0
0
0
0
0
0
0
4
F
6
1
6
…
R
esponse
I
mage
2 byte ASCII
hex
00 = live image
01 = Live image
with field of view
80 = Fault image
81 = Fault image
with field of view
2 byte ASCII
hex
Image number
8 byte ASCII hex
Length of the image data
Image
data in
the format
BMP
NOTE
A new
GI
command must be used to wait until the
RI
response to the previous request
has been sent. Otherwise a precipitously renewed
GI
command will be acknowledged
with the
RI000000000000
response.