15.4.9 GP command
– access the current configuration of the SP command
This function allows you to read out the current values that can be changed using the SP command (set
parameters for feature checks).
This is useful, for example, if you wish to read out the expected value for the "Barcode" / "Matrix code" via
the controller.
Example
Structure of the command
PLC
device
Command
Parameters
G
P
G
et
P
arameter
none
Structure of the Response
PLC
device
Response
R
G
0
0
0
8
1
5
.
0
2
.
1
4
R
esponse
G
et
Parameter
4 byte ASCII hex
Length of the result data
Data
The content of the data corresponds
with the expected values currently
set for the feature check
e.g. a date, or a combination of
expected values for different feature
checks and display settings.
NOTE
You can set the content of the datagram for output via the process interface during job
creation under
Configure interfaces → Output process interface
.