77
ZONE CONFIRMED ALARM to OUTPUTS
ZONE COMFIRMED ALARM to OUTPUT -
P168E 1-16E
Option 1 - Output 1
Option 5 - Output 5
Option 2 - Output 2
Option 6 - Output 6
Option 3 - Output 3
Option 7 - Output 7
Option 4 - Output 4
Option 8 - Output 8
If zones are programmed for near and confirmed alarms (P64E option 1 on), it is also possible to get an indication of a
Confirmed Alarm from any of the 8 Outputs using this program location. A Confirmed Alarm is the second alarm from a
different zone to the one that caused the Near Alarm and must happen within 45 minutes of the near alarm.
TIME ZONES
HOLIDAYS
HOLIDAYS -
P170E 1-8E (DDMMYY)
It is possible to pre-program up to 8 holidays. Holidays can override the time-zone function on the programmed day. For
example, if an output was automatically controlled by a time-zone, the pre-programmed holidays can stop the output
from turning on or off on a holiday. A holiday consists of a single day programmed by Date/Month/Year (DDMMYY). The
holiday begins at the start of the day (00:00:00) and finishes immediately before midnight (23:59:59) on the
programmed date. Holidays can be programmed in any order (although for simplicity it is recommended that they are
programmed in chronological order) and the panel automatically removes them once the day ends. If you wish to
manually remove a programmed holiday you must program in 000000 at the holiday location. If the holiday date you are
attempting to enter is older than the current date the panel will not save the data eg if the current date was 111204
(11th of December 2004) and you tried to enter in 101204 (10th of December 2004) the panel will not save the
programmed holiday as the day has already elapsed.
TIME ZONE DAYS
TIMEZONE DAYS -
P171E 1-8E
Option 1 - Sunday
Option 2 - Monday
Option 3 - Tuesday
Option 4 - Wednesday
Option 5 - Thursday
Option 6 - Friday
Option 7 - Saturday
Option 8 - Invert
The Time-zone days are the days that the time-zone will be active. You can select any combination of the days, eg days
2,3,4,5,6 for Monday to Friday or 1&7 for Saturday & Sunday, etc. The invert function selects all times outside those
selected. There are 8 Time-zones that can be programmed.
TIME ZONE START TIME
TIMEZONE START TIME -
P172E 1-8E (HHMM)
The Time-zone start time is when the time-zone begins. It would normally be set to the beginning of the day, eg if you
were automatically arming and disarming an area with a time-zone and you wanted it to disarm when the time-zone
started you would set the start time to about 0830. The start time is programmed in 24 hour format (eg 0000-2359).
If you are setting up the time-zone during the active period (eg if the time-zone goes from 0830-1700 and the current
time is 1200) you will have to wait until the next minute expires before the panel will update the time-zone status. You
can see if the time-zone is active at location P200E4E.
TIME ZONE END TIME
TIMEZONE END TIME -
P173E 1-8E (HHMM)
The Time-zone end time is when the time-zone finishes. It would normally be set to the end of the day, eg if you were
automatically arming and disarming an area with a time-zone and you wanted it to arm when the time-zone ended you
would set the end time to about 1700. The Time-zone end is active at the end of the programmed minute eg if the time-
zone end time was set to 1700, the actual time that the time-zone operates will be at 17:01. The end time is programmed
in 24 hour format (eg 0000-2359)