28
ACCESSING PROGRAM MODE
HOW TO PROGRAM USING LED KEYPADS
The programming sequence follows this pattern;
<
PROGRAM
> - <1,2 or 3 digit address> - <
ENTER
>
(Program Address)
1 short beep if OK - 1 long beep if error, THEN
<
PROGRAM
> - <1,2 or 3 digit sub-address> - <
ENTER
>
(Sub-Address)
3 short beeps if OK - 1 long beep if error
The LED’s will display current value or status
Enter the new value or option
<New Value> - <
ENTER
>
3 short beeps if OK - 1 long beep if error
Throughout this manual you will see program instructions expressed as
P 1 E 1-100 E
Using the above example the <P> represents the
PROGRAM
key and <E> represents the
ENTER
key.
<1> refers to the address for programming User Codes and <1-100> refers to Users 1-100.
ACCESS TO PROGRAMMING ON POWER UP (INSTALLER MODE)
When power is applied to the controller for the first time and with the panel tamper input open, the panel will
inhibit tamper alarms and ready the panel to enter
INSTALLER PROGRAM MODE
(unless the Installer Lock-out at
address P25E10E Option 8 has previously been enabled). At this point you can go to any keypad which is connected
to the panel and press
<PROGRAM> <ENTER>
which will automatically put that keypad into full Program mode.
The Program LED will now be Flashing (NOTE: Only one keypad can be in Program mode at any time).
ACCESS TO INSTALLER PROGRAM MODE FROM RUN MODE
Before you can enter Installer program mode from normal operating mode, the panel must not be Armed or in Stay
mode. Program mode access is inhibited if any part of the system is Armed.
Press <
PROGRAM
> - <
Installer Code
> - <
ENTER
>
Program light will Flash
Note: Default Installer Code (P25E1E) is 000000.
You are now in Installer Program Mode. Any program addresses may be viewed or changed in this mode.
ACCESS TO CLIENT PROGRAM MODE FROM RUN MODE
Press <
PROGRAM
> - <
Master User Code
> - <
ENTER
>
Program light On Steady
Note: Default Master User Code is code # 1 (P1E1E) which is 1234.
You are now in Client Program Mode. Access to certain program locations is limited while in Client mode (see the
options at address P5E). Each User can have different privileges based on the options assigned to the User at address
P5E. If no options are set at address P5E for a user, they will not be allowed access to Client program Mode.
RESETTING BACK TO FACTORY DEFAULT SETTINGS
(From Install Mode Only)
There are two addresses that allow you to reset the panel back to the factory defaults. The first resets just User
Codes, Installer Code & Telephone Numbers. The Second resets all programming back to the factory Defaults.
e.g. To reset All System defaults:
Press <
PROGRAM
> - <
P200E10E
> - <
ENTER
>
3 short beeps if OK - 1 long beep if error