96
P25E
13E
Misc. User Options
Miscellaneous User Options
Page 48
(Default = )
1 = Code Required to View Memory
2 = Cancel Handover Zone Function in Stay Mode
3 = Output Control from Keypad is Disabled when Armed
4 = Keypad Codes are Disabled During Entry Delay
5 = No Keypad Indications while Armed
6 = Monitored KP Buss Output Board
7 = Enable Keypad Tamper Switch Alarms
8 = Limit Events & Dialler to 3 of any one type
Setting Real Time Clock
P26E
1E
Real Time Hour/Minute -
Value 0-2359
Page 48
P26E
2E
Real Time Day of Week -
Value 1-7 (1=Sunday, 2=Monday ,etc)
P26E
3E
Real Time Date/Month/Year -
Value DDMMYY (eg 020904 = 2nd Sept 2004)
P26E
4E
Daylight Saving is Active
(If LED #1 is On, Daylight Saving is currently active) Turn this bit ON if you are in Daylight
Saving Time when the panel is installed.
Daylight Saving settings
P27E
1E
Daylight Saving Start Sunday -
Value 0-5 - Default = 1 (0 = DLS disabled, 5 = last Sunday of Month)
Page 48
2E
Daylight Saving End Sunday -
Value 0-5 - Default = 1 (0 = DLS disabled, 5 = last Sunday of Month)
P28E
1E
Daylight Saving Start Month -
Value 1-12 - Default = 10
2E
Daylight Saving End Month -
Value 1-12 - Default = 4
P29E
1E
Daylight Saving Start Hour -
Value 0-23 - Default = 2
2E
Daylight Saving End Hour -
Value 0-23 - Default = 2
OUTPUT
Programming Output Options “A”
P34E
1-8E
Options “A” for Outputs 1-8
1 = Invert Output
Page 49
(Default = All Off)
2 = Flash Output
3 = Single Pulse to Output
4 = Lockout Output
5 = DTMF Remote Control can operate Output
6 = User Can operate this Output
7 = “Control” button Can Operate Output
8 = Chime Alarms will Flash this Output (linked to Pulse Timer)
Programming Output Options “B”
P35E
1-8E
Options “B” for Outputs 1-8
1 = Mains Fail to Output (Operates when P25E6E time expires)
Page 50
(Default O/P’s 1&2 = 7)
2 = Fuse Failure to Output
(Default O/P’s 3-8 = All Off)
3 = Battery Low to output
4 = Telephone Line Failure to Output
5 = Supervised Radio Signal Failure
6 = Sensor-Watch Alarm
7 = System Tamper to Output
8 = Receiver Fail
Programming Output Options “C”
P36E
1-8E
Options “C” for Outputs 1-8
1 = Walk Test Pulse to Output
Page 50
(Default = 1)
2 = Pulse Output every 5 seconds when Disarmed
3 = Pulse Output on Kiss-off Following Arming
4 = Pulse Output on Kiss-off Following a Zone Alarm
5 = Spare
6 = Spare
7 = Spare
8 = Spare
Programming Output Options “D”
P37E
1-8E
Options “D” for Outputs 1-8
1 = Siren Driver to Output (requires a horn speaker, outputs 1&2)
Page 50
(Default = All Off)
2 = Output Reset-Chime timers are in minutes (off for seconds-1/10th seconds)
3 = Output ‘silenced’ for 10 seconds on key-press if alarm
4 = Turn Output OFF during Two Way Voice Mode
5 = Spare
6 = Spare
7 = Spare
8 = Monitored Output (can tell if siren cable is cut, outputs 1&2 only)
Output ON Delay Time
P38E
1-8E
Output 1-8 ON Delay Time -
0-9999 Seconds (Default = 0 Sec)
Page 51
Output Pulse Time
P39E
1-8E
Output 1-8 Pulse Time -
0-255;1/10th Sec increments (Default =2 which is 0.2 sec)
Page 51