70
generated. This feature is designed to detect a faulty zone that is not operating normally or one that has had
it’s detection area blocked. If a detector has this option turned on and it doesn’t operate when disarmed,
the timer at location P163E will start to count down. The timer is stopped when the area assigned to the
zone is armed and resumes with the saved value when disarmed again. The timer is reset back to the
original value every time the zone operates while disarmed.
Option 4
Zone is a Soak Test Zone
- If a zone is suspected of being faulty and is causing false alarms, you can turn it
into a Soak Test Zone and it will still be monitored for alarms when armed but it will not cause the sirens to
sound or report to the dialler. The Soak Test zone will still be logged in the event memory however so it is
possible to check the activity of the zone, via the memory, and after a suitable period of no alarms it can be
re-instated as part of the alarm by removing the Soak Test option.
Option 5
Zone will report to Area B Account Code
- If a zone is in Areas A & B and it goes into alarm, it will default to
reporting on the Area A Account Code (see P62E). By turning this option on when a zone is in both areas it
will report to Area B account Code.
Option 6
Zone will Not Report 24 Hour Alarms via Dialler
- If this option is turned on and the zone is set as a 24
Hour type, when an alarm is generated, the alarm will not be transmitted to the monitoring station via the
dialler.
Option 7
Pulse Output on Kiss-off Following a Zone Alarm
- If this option is turned on, when an alarm is reported to
monitoring and is kissed off, any Output with Option 4 ON at P36E will pulse for 2 seconds.
Option 8
Exit Terminator Zone
- If this option is on, when the zone unseals during the exit delay time and then seals
again the panel will cancel any remaining exit delay time and arm in 3 seconds from the time the zone was
sealed. The zone can also be left unsealed at the time of arming and will terminate the exit delay 3 seconds
after it is sealed. Once armed, the exit terminator zone will cause an alarm if unsealed again (the alarm will
be delayed if an entry delay is programmed (P144E), otherwise it will be instant).
ZONE EOL (End-of-Line) OPTIONS
There are 8 hardwired zone inputs on the panel. Each of these inputs can have different EOL (End-of-Line) configurations
if desired. The input can be a short circuit wire loop (Type 0), one of 11 different single resistor values (Types 1-11), can
provide 8 zones with tamper (Types 12,13), zone doubling to allow for up to 16 zones plus tamper (Type 14), or zone
doubling without tamper (Type 15). See chart on page 6 for the resistor combinations and colour codes.
NOTE: If using
vibration settings 1-8 (see P126E below) then this location can ONLY be set to type 3.
ZONE EOL (End-of-Line) OPTIONS
- P125E 1-8E
Option 0 - Short Circuit Loop
Option 8 - 6k8
Option 1 - 1k
Option 9 - 10k
Option 2 - 1k5
Option 10 - 12k
Option 3 - 2k2
Option 11 - 22k
Option 4 - 3k3
Option 12 - 2k2 // 4k7
Option 5 - 3k9
Option 13 - 3k3 // 6k8
Option 6 - 4k7
Option 14 - 2k2 // 4k7 // 8k2
Option 7 - 5k6
Option 15 - 4k7 // 8k2
ZONE RESPONSE TIME
There are 8 hardwired zone inputs on the panel. The response time (how quickly the input responds to an input trigger)
can be varied for each zone. The first 8 settings are very fast response times normally used when vibration sensors are
connected to a zone input.
Response Settings 1-8 (vibration) can only be applied to zones 1-8 and the zone EOL setting
(P125E) must be set to type 3 (2k2)
. Zone doubling is not available when vibration settings are used.
The response settings 9-26 start at about 200 ms for setting 9 through to 1.05 sec for setting 26. If zone doubling is
turned on, both zones on an input will have the same response time (eg zones 1 & 9 would have the same time).
ZONE RESPONSE TIME
- P126E 1-8E
Response Setting 1 - Highest Vibration setting
Response Setting 5 - Middle Vibration setting
Response Setting 2 - Middle Vibration setting
Response Setting 6 - Middle Vibration setting
Response Setting 3 - Middle Vibration setting
Response Setting 7 - Middle Vibration setting
Response Setting 4 - Middle Vibration setting
Response Setting 8 - Lowest Vibration setting
Response Setting 9 - 200 ms
Response Setting 18 - 650 ms
Response Setting 10 - 250 ms
Response Setting 19 - 700 ms