45
DURESS DIGIT
DURESS DIGIT
- P25E 2E (Value can be 1-9, 0 = Duress Disabled)
The duress digit can be a number from 1-9 (a value of “0” means the duress function is disabled).
To create a duress alarm the duress digit must be entered before a valid user code (eg If the code was “123” and the
duress number was “4”, then entering a code of <4123> <ENTER> would create a duress alarm).
DIAL REPORT DELAY
DIAL REPORT DELAY
- P25E 3E (0-255 Seconds)
If this address is set to 0, there will be no report delay. If it is set to any value other than 0 then a delay equal to the
programmed value will stop the panel from reporting an alarm until this delay time expires.
RADIO ZONE SUPERVISED TIMER
RADIO ZONE SUPERVISED TIMER
-
P25E 4E (Value 0-9999 Minutes)
If a radio detector is capable of sending regular supervisory signals to the panel and the zone type is set for
“Supervised Signal Active”, this timer sets how long a period has to elapse with no received transmissions before a
supervisory failure alarm is generated.
TWO TRIGGER TIMER
TWO TRIGGER TIMER -
P25E 5E (0-255 Seconds)
If a zone is set to two trigger, the zone has to cause an alarm twice within the two trigger time period to cause an
alarm. If multiple zones are set to two trigger, an alarm will be generated it two zones trigger once each within the
two trigger time period. If a two trigger zone goes into alarm but remains in alarm for longer than the two trigger time
period (ie detector failure or cable cut) an alarm will be generated.
MAINS FAIL REPORTING DELAY
MAINS FAIL REPORTING DELAY -
P25E 6E (0-9999 Seconds)
If a Mains Failure occurs this timer delays the reporting of Mains Failure to a Monitoring Station. If the mains power
returns before the timer expires then no report is sent. If Mains Failure is assigned to an output, this delay must expire
before the output will turn on.
RECEIVER FAIL DELAY
RECEIVER FAIL DELAY -
P25E 7E (0-9999 Seconds)
If supervised radio detectors are used, the receiver will be seeing regular transmissions. Because of this, the panel can
monitor receiver activity to check that the receiver is still working. If the panel does not receive any signals within this
time period a receiver failure alarm will be generated. If set to 0, the receiver monitoring will be turned off.
UPLOAD/DOWNLOAD SITE CODE NUMBER
UPLOAD/DOWNLOAD SITE CODE NUMBER -
P25E 8E (8 characters)
The upload/download site code number must be entered if the panel is set for auto-answer as this provides a security
access level to the panel. The number can be up to 8 characters in length. Valid characters for this number are 0-9,B-F.
See chart on page 55 for details of how to program the characters B-F.