![Asentria TeleBoss 830 Скачать руководство пользователя страница 65](http://html.mh-extra.com/html/asentria/teleboss-830/teleboss-830_user-manual_2981744065.webp)
TeleBoss 830 2.11.370 STD User Manual
Page 65
Maximum Retries
This field defines the maximum number of times to retry a failed connection for all phone numbers present.
The default setting is 3.
Carrier Detect / Login Sequence Timeout (sec)
These fields set standard login timeouts, from 0 to 65535 seconds. The default setting is 60 seconds for
Carrier Detect, and 30 seconds for Login Sequence.
Dialout Modem Init String
This field sets the modem initialization string (maximum length 48 characters).
IP Address to Suggest
This field sets an IP to try to acquire, if defined. The default setting is 0.0.0.0.
Firewall
This is an ON/OFF toggle to enable or disable the PPP Modem firewall. The default is on.
Maximum Dialout Failures
Each time a call is attempted, the number's failure count is checked before dialing. If the Maximum Dialout
Failure count is reached, then the number will not be dialed until its blackout period expires, or the unit is
restarted. After dialing, if the call is a failure, then the called number's failure count is incremented. When it
reaches the maximum allowed failures, a blackout timer is set for 2 hours. After dialing, if the call is
successful then called number's failure count is set to 0. The allowed values are 0 - 100 inclusive. If this setting
is set to "0", failures are ignored and no blackout will occur. The default is 15.
PPP Hosting Settings
This menu is for configuring settings for hosting a PPP connection on the POTs Dial-Up Modem.
TeleBoss 830 - PPP Hosting Settings
A) PPP Hosting Enabled [OFF]
B) Idle Connection Disconnect (sec) [60]
C) Local (Device) IP Address [192.168.105.1]
D) Remote (Caller) IP Address [192.168.105.2]
E) Firewall [ON]
PPP Hosting Enabled
This is an ON/OFF toggle to enable inbound PPP connection hosting. The default setting is OFF.
Idle Connection Disconnect (sec)
This field sets the number of seconds (0 to 65535) to wait before disconnecting an idle connection. A setting
of 0 means the unit does not disconnect due to an idle connection. The default setting is 60 seconds.
Local (Device) IP Address
This option sets the IP address of the TeleBoss for the PPP session. The default is 192.168.105.1
Remote (Caller) IP Address
This field
sets the IP address of the calling device for the PPP session. The default is 192.168.105.2.
Содержание TeleBoss 830