TeleBoss 830 - Settings For Data Alarm/Filter 1
A) Alarm/Filter Enable [OFF]
B) Alarm/Filter Mode [ALARM]
C) Alarm/Filter Name []
D) Alarm/Filter Equation []
E) Threshold [1]
F) Auto-Clear when Threshold Reached [ON]
G) Alarm Counter Clear Interval [12 HOURS]
H) Alarm Counter Reset Time [00:00]
I) Actions []
J) Class [Info]
K) Data Alarm Trap Number [503]
L) Clear This Alarm Counter Now
Alarm/Filter Enable
This toggles each individual data event monitor ON or OFF. The default setting is OFF
Alarm/Filter Mode
This toggles between Alarm and Filter to indicate whether the TeleBoss will recognize this data event as an
Alarm and take some action, or as a Filter and either accept or reject the data string. The default setting is
ALARM.
Alarm/Filter Name
Use this field to
set the name for the event monitor. This name is reported with the specified actions. The
maximum length is 16 characters.
Alarm/Filter Equation
Set the event equation using the event fields defined in the
length is 160 characters. Refer to the
Data Alarm and Event Configuration Feature Guide
explanation of configuring data alarm equations. Contact
Threshold
This field
sets the number of times the event equation must be matched before an event is triggered. If the
event counter is allowed to grow beyond the threshold, the unit will not trigger an event again until after the
counter is reset. The default setting is 1.
Auto-Clear when Threshold Reached
This is an ON/OFF toggle to control whether the unit will clear the event counter each time the threshold is
met. The default setting is ON.
Alarm Counter Clear Interval
Use this option to
set an interval at which the unit should clear the match counter for an individual data event.
The available options are: 2 hours, 4 hours, 6 hours, 8 hours, 12 hours, Daily, and Never. The first clear
occurs at midnight. The default setting is 12 Hours.
Alarm Counter Reset Time
This field
sets the time at which the daily clear should take place if it is enabled in the Alarm Counter Clear
Interval. This value is in 24-hour format. The default setting is 00:00.