Installation and operating instructions Wilo-Rexa CUT
47
COMMISSIONING
English
active and does not need to be connected sepa-
rately.
Temperature monitoring of the three-phase AC
motor
The pump is equipped with a temperature limit as
standard (1-circuit temperature monitoring). Bi
-
metallic strips must be connected in the switch-
gear itself or via an evaluation relay. When the
threshold is reached, the pump must switch off.
Connection values: max. 250 V(AC), 2.5 A, cos φ
= 1
For this reason, no warranty claims can be accept
-
ed for any damage to the winding resulting from
unsuitable motor monitoring!
Motor compartment (motor version "P" only)
The motor compartment monitor must be con
-
nected via an evaluation relay. We recommend
the “NIV 101/A” relay for this. The threshold is
30 kOhm. When the threshold is reached, the
pump must switch off.
Connecting the pencil electrode (available as an
option) for sealing chamber control
The pencil electrode must be connected via an
evaluation relay. We recommend the “NIV 101/A”
relay for this. The threshold is 30 kOhm. When the
threshold is reached, a warning must be given or
the unit switched off.
CAUTION!
If there is only a warning, the pump could be
irreparably damaged by water ingress. We
always recommend switching the pump off!
5.6. Motor protection and activation types
5.6.1. Motor protection
The minimum requirement for motors with a free
cable end is a thermal relay/motor protection
switch with temperature compensation, differ
-
ential triggering and an anti-reactivation device
in accordance with VDE 0660 or the appropriate
national regulations.
If the pump is connected to electrical systems
in which faults frequently occur, we recommend
installing additional protective devices provided
by the customer (overvoltage, undervoltage or
phase failure relays, lightning protection etc.).
We also recommend installing a residual-current
device (RCD).
Local and national regulations must be observed
when connecting the pump.
5.6.2. Activation types
Direct activation
At full load, the motor protection should be set
to the rated current shown on the rating plate. At
partial load, we recommend that the motor pro
-
tection be set 5 % above the current measured at
the duty point.
Soft start activation
•
At full load, the motor protection should be set
to the rated current at the duty point. At partial
load, we recommend that the motor protection
be set 5 % above the current measured at the
duty point.
•
The current consumption must be below the rat
-
ed current throughout the entire operation.
•
Due to the upstream motor protection, starting or
stopping should be completed within 30 seconds.
•
To avoid power dissipation during operation,
bypass the electronic starter (soft start) once
normal operation is reached.
5.6.3. Operation with frequency converters
Operation with a frequency converter is only pos-
sible with motor version "P". Note the information
about this in the appendix.
Motor version "S" motors may not be operated
with frequency converters.
6. Commissioning
The “Commissioning” section contains all the im
-
portant instructions for the operating personnel
for starting up and operating the pump.
The following conditions must be adhered to and
monitored:
•
Type of installation
• Operating mode
•
Minimum water submersion/max. immersion
depth
These general conditions must also be checked
after a lengthy period without operation, and
any defects detected must be repaired!
Always keep this manual either by the pump
or in a place specially reserved for it, where it is
accessible for the entire operating personnel at
all times.
In order to prevent damage or serious injury when
commissioning the pump, the following points
must be observed:
•
Commissioning of the pump may only be carried
out by qualified and trained personnel in accord
-
ance with the safety instructions.
• All persons working on or with the pump must
have received, read and understood this operating
and maintenance manual.
• All safety devices and emergency cut-outs must
be connected and checked to ensure that they
work properly.
• Electrical engineering and mechanical adjust-
ments must be made by qualified personnel.
•
The pump is suitable for use under the specified
operating conditions.
•
The work area of the pump is not a recreational
area and is to be kept free of people! No persons
are allowed in the work area during start-up or
operation.
Summary of Contents for Rexa CUT
Page 5: ...Fig 9 Fig 8 1 2 3 5 4 1 2 3 4 5 5 7 5 8 6...
Page 6: ......
Page 8: ......
Page 34: ......
Page 58: ......
Page 84: ......
Page 156: ......
Page 159: ...Wilo Rexa CUT 159 2 2 1 DIN ANSI 2 2...
Page 160: ...160 WILO SE 11 2014 V05 DIN A4 2 3 VDE 0100 RCD RCD 2 4 P 2 5...
Page 165: ...Wilo Rexa CUT 165 6 4 4 5 5 1 ATV 5 2 5 3...
Page 166: ...166 WILO SE 11 2014 V05 DIN A4 S3 5 3 1 6 1 2 7 3 1 cm 4 5 5 3 2 40 C...
Page 168: ...168 WILO SE 11 2014 V05 DIN A4 3 1 3 5 3 4 5 4 5 4 1 5 5 DIN EN 60079 0...
Page 171: ...Wilo Rexa CUT 171 5 30 s 5 6 3 P S 6 6 1 VDE 6 2 6 2 1 6 2 2 2 U1 V1 U2 V2 6 3...
Page 172: ...172 WILO SE 11 2014 V05 DIN A4 6 4 II 2G Ex d IIB T4 6 5 IP 6 5 1 6 5 2 6 6 5 2 5 1...
Page 173: ...Wilo Rexa CUT 173 7 7 1 3 C 5 7 2 40 C 7 3 7 3 1 7 3 2 7 4 7 5 7 5 1 75 439 5a 5b AbfG...
Page 174: ...174 WILO SE 11 2014 V05 DIN A4 7 5 2 TA 524 02 91 689 7 5 3 8 Wilo Wilo 1 2...
Page 230: ......
Page 254: ......
Page 281: ...Wilo Rexa CUT 281 1 5 6 2 2 1 DIN ANSI 2 2...
Page 282: ...282 WILO SE 11 2014 V05 DIN A4 2 3 VDE 0100 EVO RCD RCD 2 4 P...
Page 283: ...Wilo Rexa CUT 283 2 5 2 6 2 7 80 85 A 2 8 2 9 3...
Page 287: ...Wilo Rexa CUT 287 4 3 1 15 C 5 25 C 6 4 4 5...
Page 288: ...288 WILO SE 11 2014 V05 DIN A4 5 1 ATV 5 2 5 3...
Page 291: ...Wilo Rexa CUT 291 5 4 5 4 1 5 5 DIN EN 60079 0 RCD 5 5 1 K 5 5 2...
Page 294: ...294 WILO SE 11 2014 V05 DIN A4 30 5 6 3 P S 6 6 1 VDE 6 2 6 2 1 6 2 2 2 U1 V1 U2 V2 6 3...
Page 295: ...Wilo Rexa CUT 295 6 4 Ex Ex Ex II 2G Ex d IIB T4 6 5 IP 6 5 1 6 5 2 6 6 5 2 5...
Page 296: ...296 WILO SE 11 2014 V05 DIN A4 1 7 7 1 3 C 5 7 2 40 C 7 3 7 3 1 7 3 2 7 4...
Page 297: ...Wilo Rexa CUT 297 7 5 7 5 1 75 439 5a 5b 7 5 2 TA 524 02 91 689 7 5 3 8 Wilo Wilo 1 2...
Page 299: ...Wilo Rexa CUT 299 8 2 3 3 Wilo 8 3 8 3 1 Wilo 8 3 2 8 3 3 Wilo 8 3 4 0 8 3 5 8 3 6 7 1...
Page 301: ...Wilo Rexa CUT 301 0 1 0 2 9 1 4 2 5 3 5 5 1 2 3 0 1 0 2 4 37 5 9 1 2 3 1 2 3 4 3 5 2 6 Wilo 7...
Page 306: ...306 WILO SE 11 2014 V05 DIN A4 S3 10 3 5 1 2 DIN EN 60079 1 600 10 4 Wilo...
Page 330: ......
Page 356: ......
Page 359: ...I Wilo Rexa CUT 359 2 2 1 DIN ANSI 2 2...
Page 360: ...360 WILO SE 11 2014 V05 DIN A4 2 3 VDE 0100 RCD RCD 2 4 P 2 5...
Page 361: ...I Wilo Rexa CUT 361 2 6 2 7 80 A 85 2 8 2 9 3 3 1 DIN VDE 0100 702 46 Wilo Rexa CUT...
Page 365: ...I Wilo Rexa CUT 365 6 4 4 5 5 1 5 2 5 3...
Page 366: ...366 WILO SE 11 2014 V05 DIN A4 S3 5 3 1 6 1 2 7 3 1 4 5 5 3 2...
Page 368: ...368 WILO SE 11 2014 V05 DIN A4 3 1 3 5 3 4 5 4 5 4 1 5 5 DIN EN 60079 0...
Page 371: ...I Wilo Rexa CUT 371 5 30 5 6 3 P S 6 6 1 VDE 6 2 6 2 1 6 2 2 2 U1 V1 U2 V2 6 3...
Page 372: ...372 WILO SE 11 2014 V05 DIN A4 6 4 Ex II 2G Ex d IIB T4 6 5 IP 6 5 1 6 5 2 6 6 5 2 5 1...
Page 374: ...374 WILO SE 11 2014 V05 DIN A4 91 689 EWG 7 5 3 8 Wilo Wilo 1 2...
Page 382: ...382 WILO SE 11 2014 V05 DIN A4 S3 10 3 5 Ex 1 2 DIN EN 60079 1 600 10 4 Wilo...
Page 383: ......