Functions
7.7 Application-specific functions
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
387
7.7.6
Automatic restart
The automatic restart includes two different functions:
●
The inverter automatically acknowledges faults.
●
After a fault occurs or after a power failure, the inverter automatically switches the motor
on again.
The inverter interprets the following events as power failure:
●
The inverter signals fault F30003 (DC-link undervoltage), as the line supply voltage of the
inverter has briefly failed.
●
The inverter power supply has failed for a long enough time so that the inverter has been
switched-off.
WARNING
Danger to life due to the automatic machine restart
When the "automatic restart" function is active (p1210 > 1), the motor automatically starts
after a power failure. The movements that the machine executes may result in death,
serious injury or material damage.
•
Block the machine to prevent unintentional access.
•
Before working on the machine switch the automatic restart mechanism off.
Setting the automatic restart
Proceed as follows to commission the automatic restart:
If it is possible that the motor is still rotating for a longer period of time after a power failure or
after a fault, then in addition, you must activate the "flying restart" function, see Flying restart
(Page 385).
Using p1210, select the automatic restart mode that best suits your application.
Figure 7-20 Selecting the automatic restart mode
Summary of Contents for SINAMICS G120P
Page 1: ......
Page 2: ......
Page 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Page 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Page 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Page 496: ......