![Siemens SINAMICS G120P Operating Instructions Manual Download Page 224](http://html.mh-extra.com/html/siemens/sinamics-g120p/sinamics-g120p_operating-instructions-manual_378189224.webp)
Operation
6.8 Communication via RS485
Inverter cabinet units
224
Operating Instructions, 12/2014, A5E32923362A
No.
Description
6B hex
No change access for a closed-loop controller that is enabled (operating state of the in-
verter prevents a parameter change)
86 hex
Write access only for commissioning (p0010 = 15) (operating state of the inverter prevents
a parameter change)
87 hex
Know-how protection active, access locked
C8 hex
Change request below the currently valid limit (change request to a value that lies within
the "absolute" limits, but is however below the currently valid lower limit)
C9 hex
Change request above the currently valid limit (example: a parameter value is too large for
the inverter power)
CC hex Change request not permitted (change is not permitted as the access code is not availa-
ble)
Parameter number
Parameter numbers < 2000 PNU = parameter number.
Write the parameter number into the PNU (PKE bit 10 ... 0).
Parameter numbers
≥ 2000
PNU = parameter number - offset.
Write the parameter number minus the offset into the PNU
(PKE bit 10 … 0).
Write the offset in the page index (IND bit 15 … 8).
Table 6- 17 Offset and page index of the parameter numbers
Parameter number Offset Page index
Hex
Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8
0000 … 1999
0
0 hex
0
0
0
0
0
0
0
0
2000 … 3999
2000 80 hex
1
0
0
0
0
0
0
0
6000 … 7999
6000 90 hex
1
0
0
1
0
0
0
0
8000 … 9999
8000 20 hex
0
0
1
0
0
0
0
0
10000 … 11999
10000 A0 hex
1
0
1
0
0
0
0
0
20000 … 21999
20000 50 hex
0
1
0
1
0
0
0
0
30000 … 31999
30000 F0 hex
1
1
1
1
0
0
0
0
60000 … 61999
60000 74 hex
0
1
1
1
0
1
0
0
Indexed parameters
For indexed parameters, you must write the index as hex value into the subindex (IND
bit 7 … 0).
Summary of Contents for SINAMICS G120P