Electrical installation
4.6 Power connections
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
69
Figure 4-6
Opening the connection to the basic interference suppression module, frame size GX
The connection is opened as follows:
1.
Release the left-hand housing flap by rotating latch
①
and opening the housing flap.
2.
Release the two screws
②
; they are captive.
3.
Release screws
③
and
④
; however, do not remove the screws.
4.
Swivel the connection clip
⑤
around the axis of rotation of screw
③
towards the left, until
the connection clip can be fastened using screw
⑥
.
5.
Tighten screws
③
and
⑥
with 6 Nm.