Operation
6.8 Communication via RS485
Inverter cabinet units
244
Operating Instructions, 12/2014, A5E32923362A
6.8.4.2
Supported services and objects
BIBBs used by the inverter
The BIBBs (BIBB: BACnet Interoperability Building Block) are a collection of one or several
BACnet services. The BACnet services are subdivided into A and B devices. An A device
operates as client and a B device as server.
The inverter is a server and therefore operates as B device, as "BACnet Application Specific
Controller" (B-ASC).
The CU230P-2 HVAC uses the BIBBs listed below.
Overview of the BIBBs used by CU230P-2 HVAC and associated services
Short designation BIBB
Service
DS-RP-B
Data Sharing-ReadProperty-B
ReadProperty
DS-RPM-B
Data Sharing-ReadMultipleProperty-B ReadPropertyMultiple
DS-WP-B
Data Sharing-WriteProperty-B
WriteProperty
DM-DDB-B
Device Management-Dynamic Device
Binding-B
•
Who-Is
•
I-Am
DM-DOB-B
Device Management-Dynamic Object
Binding-B
•
Who-Has
•
I-Have
DM-DCC-B
Device Management-
DeviceCommunicationControl-B
DeviceCommunicationControl
DS-COV-B
Data Sharing-COV-B
•
SubscribeCOV,
•
ConfirmedCOVNotification,
•
UnConfirmedCOVNotification
The inverter can simultaneously process up to 32 SubscribeCOV services. These can all
refer to the same object instances - or different object instances.
SubscribeCOV monitors the property changes of the following objects:
●
Analog Input (AIxx),
●
Analog Output (AOxx),
●
Analog Value (AVxx),
●
Binary Value (BVxx) and
●
Multi-state Input (MSIxx)
Note
SubscribeCOV services are not retentive; i.e. the master must re-initiate the SubscribedCOV
services when restarting the CU.
Summary of Contents for SINAMICS G120P
Page 1: ......
Page 2: ......
Page 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Page 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Page 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Page 496: ......