Alarms, faults and system messages
9.5 List of alarms and faults
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
447
Number Cause
Remedy
A05000
A05001
A05002
A05004
A05006
Power Module overtemperature
Check the following:
- Is the ambient temperature within the defined limit values?
- Are the load conditions and duty cycle configured accordingly?
- Has the cooling failed?
F06310
Supply voltage (p0210) incorrectly
set
Check the set supply voltage and if required change (p0210).
Check the line voltage.
F07011
Motor overtemperature
Reduce the motor load.
Check the ambient temperature.
Check the wiring and connection of the sensor.
A07012
I2t Motor Module overtemperature Check and if necessary reduce the motor load.
Check the motor's ambient temperature.
Check the thermal time constant p0611.
Check the overtemperature fault threshold p0605.
A07015
Motor temperature sensor alarm
Check that the sensor is connected correctly.
Check the parameter assignment (p0601).
F07016
Motor temperature sensor fault
Make sure that the sensor is connected correctly.
Check the parameterization (p0601).
Deactivate the motor temperature sensor fault evaluation (p0607 = 0).
F07086
F07088
Switching over units: Parameter
limit violation
Check the adapted parameter values and if required correct them.
F07320
Automatic restart aborted
Increase the number of restart attempts (p1211). The actual number of
start attempts is shown in r1214.
Increase the wait time in p1212 and/or monitoring time in p1213.
Connect an ON command (p0840).
Increase the monitoring time of the power unit or switch off (p0857).
Reduce the wait time for resetting the fault counter p1213[1] so that fewer
faults are registered in the time interval.
A07321
Automatic restart active
Explanation: The automatic restart (AR) is active. During voltage recovery
and/or when remedying the causes of pending faults, the drive is auto-
matically switched back on.
F07330
Search current measured too low
Increase the search current (p1202), check the motor connection.
A07400
DC-link voltage maximum control-
ler active
If it is not desirable that the closed-loop controller intervenes:
•
Increase the ramp-down times.
•
Deactivate the Vdc_max control (p1240 = 0 for vector control,
p1280 = 0 for V/f control).
A07409
V/f control, current limiting control-
ler active
The alarm automatically disappears after one of the following measures:
•
Increase the current limit (p0640).
•
Reduce the load.
•
Slow down the ramp-ups for the setpoint speed.
F07426
Technology controller actual value
limited
•
Adapt the limits to the signal level (p2267, p2268).
•
Check the actual value scaling (p2264).
Summary of Contents for SINAMICS G120P
Page 1: ......
Page 2: ......
Page 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Page 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Page 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Page 496: ......