Settings in the inverter
After you have completed the basic commissioning, you must set the following P1-specific
parameters in the inverter:
Parameter
Description
p2030 = 8
Communication protocol for P1.
With this setting, the inverter sets parameters p2020 and p2021 as follows:
•
p2020 = 5: Baud rate 4800 bit/s
•
p2021 = 1 … 99: Slave address (factory setting = 99).
p0840 = 2090.0
Wire ON/OFF1 to control word 1 bit 0
p0852 = 2090.3
Wire the signal for Enable operation to control word 1 bit 3
p1070 = 2050.1
Connect the signal for the main setpoint to the communication interface
p2103.0 = 2090.7
Connect the first signal source for acknowledgment to the communication
interface
p2051.0 = 52.0
Send status word via the communication interface
p2051.1 = 63.0
Send actual speed value via the communication interface
p0971 = 1
Permanently save the settings in the inverter
Note
Address 99 (to all)
No matter their address, all FLN devices answer telegrams with address 99.
Summary of Contents for SINAMICS G120P
Page 1: ......
Page 2: ......
Page 8: ...Preface Inverter cabinet units 8 Operating Instructions 12 2014 A5E32923362A ...
Page 16: ...Table of contents Inverter cabinet units 16 Operating Instructions 12 2014 A5E32923362A ...
Page 432: ...Application examples Inverter cabinet units 432 Operating Instructions 12 2014 A5E32923362A ...
Page 496: ......