Commissioning
5.5 Procedure for commissioning via STARTER
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
161
Configuring the drive unit properties
Figure 5-22 Configuring the drive unit properties
⇒
Under Standard:, choose the appropriate standard for your motor,
whereby the following is defined:
●
IEC motor (50 Hz, SI unit): Line frequency 50 Hz, motor data in kW
●
NEMA motor (60 Hz, US unit): Line frequency 60 Hz, motor data in hp
●
NEMA motor (60 Hz, SI unit): Line frequency 60 Hz, motor data in kW
⇒
Under Power unit application: If the load cycle "[1] Load duty cycle with low overload for
vector drives" is permanently set.
⇒
Click on Continue >